Schneider-Electric
SR3PACKBD
Tariff code: 8536419089
Link to the manufacturers site: SR3PACKBD - modular smart relay Zelio Logic - “discovery” pack - 10 I O - 24 V DC
Main
Range of produc: Zelio Logic
Product or component type: Modular discovery packs
Discrete input number: 6 conforming to IEC 61131-2 Type 1
Number of outputs: 4 relay
Complementary
Kit composition: SR3B101BD; Cable PC SR2USB01 for connection to PC
input/output number: 10
Local display: With
Number or control scheme lines: 120 with ladder programming; 0…200 with FBD programming
Cycle time: 6…90 ms
Backup time: 10 years at 25 °C
Clock drift: 12 min/year at 0…55 °C; 6 s/month at 25 °C
Checks: Program memory on each power up
[Us] rated supply voltage: 24 V
Supply voltage limits: 19.2…30 V
Maximum supply current: 100 mA (with extensions); 100 mA (without extension)
Power dissipation in W: 3 W without extension; 8 W with extensions
Reverse polarity protection: With
discrete input type: Resistive
Discrete input voltage: 24 V DC
Discrete input current: 4 mA
Counting frequency: 1 kHz for discrete input
Voltage state 1 guaranteed: >= 15 V for I1...IA and IH...IR discrete input circuit; >= 15 V for IB...IG used as discrete input circuit
Voltage state 0 guaranteed: <= 5 V for I1...IA and IH...IR discrete input circuit; <= 5 V for IB...IG used as discrete input circuit; <= 5 V
Current state 1 guaranteed: >= 1.2 mA (IB...IG used as discrete input circuit); >= 2.2 mA (I1...IA and IH...IR discrete input circuit)
Current state 0 guaranteed: <= 0.5 mA (IB...IG used as discrete input circuit); <= 0.75 mA (I1...IA and IH...IR discrete input circuit)
Input compatibility: 3-wire proximity sensors PNP for discrete input
analogue input number: 4
analogue input type: Common mode
Analogue input range: 0...24 V; 0...10 V
Temperature probe type: NTC 10k at 25 °C; NTC 1000k at 25 °C; KTY81 210/220/221/222/250; Pt 500
Maximum permissible voltage: 30 V for analogue input circuit
analogue input resolution: 8 bits
LSB value: 39 mV for analogue input circuit
Conversion time: Smart relay cycle time for analogue input circuit
Conversion error: +/- 5 % at 25 °C for analogue input circuit; +/- 6.2 % at 55 °C for analogue input circuit
Repeat accuracy: +/- 2 % at 55 °C for analogue input circuit
Operating distance: 10 m between stations, with screened cable (sensor not isolated) for analogue input circuit
Input impedance: 12 kOhm for IB...IG used as analogue input circuit; 12 kOhm for IB...IG used as discrete input circuit; 7.4 kOhm for I1...IA and IH...IR discrete input circuit
Output voltage limits: 24...250 V AC (relay output); 5...30 V DC (relay output)
Contacts type and composition: NO for relay output
Output thermal current: 8 A for all 4 outputs for relay output
Electrical durability: AC-12: 500000 cycles at 230 V, 1.5 A for relay output conforming to IEC 60947-5-1; AC-15: 500000 cycles at 230 V, 0.9 A for relay output conforming to IEC 60947-5-1; DC-12: 500000 cycles at 24 V, 1.5 A for relay output conforming to IEC 60947-5-1; DC-13: 500000 cycles at 24 V, 0.6 A for relay output conforming to IEC 60947-5-1
Switching capacity in mA: >= 10 mA at 12 V (relay output)
Operating rate in Hz: 0.1 Hz (at Ie) for relay output; 10 Hz (no load) for relay output
Mechanical durability: 10000000 cycles for relay output
[Uimp] rated impulse withstand voltage: 4 kV conforming to EN/IEC 60947-1 and EN/IEC 60664-1
clock: With
Response time: 10 ms (from state 0 to state 1) for relay output; 5 ms (from state 1 to state 0) for relay output
Connections - terminals: Screw terminals, 1 x 0.2...1 x 2.5 mm² (AWG 25...AWG 14) semi-solid; Screw terminals, 1 x 0.2...1 x 2.5 mm² (AWG 25...AWG 14) solid; Screw terminals, 1 x 0.25...1 x 2.5 mm² (AWG 24...AWG 14) flexible with cable end; Screw terminals, 2 x 0.2...2 x 1.5 mm² (AWG 24...AWG 16) solid; Screw terminals, 2 x 0.25...2 x 0.75 mm² (AWG 24...AWG 18) flexible with cable end
Tightening torque: 0.5 N.m
Overvoltage category: III conforming to IEC 60664-1
Net weight: 0.7 kg
Environment
Immunity to microbreaks: 1 ms
product certifications: GL; UL; CSA; GOST; C-Tick
Standards: IEC 60068-2-27 Ea; IEC 60068-2-6 Fc; IEC 61000-4-3; IEC 61000-4-6 level 3; IEC 61000-4-11; IEC 61000-4-5; IEC 61000-4-2 level 3; IEC 61000-4-12; IEC 61000-4-4 level 3
IP degree of protection: IP20 (terminal block) conforming to IEC 60529; IP40 (front panel) conforming to IEC 60529
Environmental characteristic: EMC directive conforming to IEC 61000-6-2; EMC directive conforming to IEC 61000-6-3; EMC directive conforming to IEC 61000-6-4; EMC directive conforming to IEC 61131-2 zone B; Low voltage directive conforming to IEC 61131-2
Disturbance radiated/conducted: Class B conforming to EN 55022-11 group 1
Pollution degree: 2 conforming to IEC 61131-2
Ambient air temperature for operation: -20…40 °C in non-ventilated enclosure conforming to IEC 60068-2-1 and IEC 60068-2-2; -20…55 °C conforming to IEC 60068-2-1 and IEC 60068-2-2
Ambient air temperature for storage: -40…70 °C
Operating altitude: 2000 m
Maximum altitude transport: 3048 m
Relative humidity: 95 % without condensation or dripping water
Packing Units
Unit Type of Package 1: PCE
Number of Units in Package 1: 1
Package 1 Height: 6.2 cm
Package 1 Width: 15.5 cm
Package 1 Length: 23.3 cm
Package 1 Weight: 390 g
Unit Type of Package 2: S03
Number of Units in Package 2: 10
Package 2 Height: 30 cm
Package 2 Width: 30 cm
Package 2 Length: 40 cm
Package 2 Weight: 4.409 kg
Offer Sustainability
Sustainable offer status: Green Premium product
REACh Regulation: Reference contains Substances of Very High Concern above the threshold
EU RoHS Directive: Pro-active compliance (Product out of EU RoHS legal scope)
Mercury free: Yes
China RoHS Regulation: X
RoHS exemption information: Yes
Environmental Disclosure: ENVPEP060406EN
Circularity Profile: ENVEOLI0604006EN
WEEE: The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
PVC free: Yes
© 2018 Alplan Kft.