Schneider-Electric
RMNF22TB30
Tariff code: 8536490099
Link to the manufacturers site: RMNF22TB30 - Zelio Control háromfázisú fázis- és feszültségfigyelő relé, NFC, 2CO, 8A, multifunkciós, ki- és bekapcsolás késlelt.
Main
Range of produc: Harmony Control Relays
Relay type: Control relay
Product or component type: 3-phase control relay
Network number of phases: 3 phases
Relay name: RMNF22
Relay monitored parameters: Phase sequence; Phase failure detection; Overvoltage detection; Undervoltage detection; Overfrequency and underfrequency; Asymmetry
Operating system: Android
software version: V4.4 and above
Software designation: Zelio NFC (downloadable from Google Play store)
Product compatibility: NFC enabled mobile device
Time delay type: On-delay 0.1 s...60 min; Off-delay 0.1 s...60 min
Switching capacity in VA: 2000 VA
Connections - terminals: Screw connectors
[Uc] control circuit voltage: 208...480 V; 120...277 V
[In] rated current: 8 A
Complementary
Maximum operating frequency: 13.56 MHz
nominal power: 0.0002 mW
Reset time: 1500 ms at maximum voltage
Maximum switching voltage: 250 V AC
Minimum switching current: 100 mA at 6 V
Maximum switching current: 8 A AC
Supply voltage limits: 166.4…576 V AC line to line; 96…332.4 V AC line to neutral
Power consumption in VA: 4 VA at 480 V AC 60 Hz
On-load factor: 100 %
Supply frequency: 50...60 Hz +/- 10 %
Output contacts: 2 C/O
Setting accuracy of the switching threshold: +/- (1.5 % + 1 V)
Setting accuracy of time delay: +/- 3 % for 10 s...60 min time delay range; +/- 300 ms for 0...10 s time delay range
Hysteresis: 3 % of fixed for phase failure detection
Alarm threshold: 166...576 V adjustable overvoltage and undervoltage detection (line to line); 96...332 V adjustable overvoltage and undervoltage detection (line to neutral); 5...150 V adjustable asymmetry; 45...66 Hz adjustable overfrequency or underfrequency
run-up delay at power-up: 650 ms
Maximum measuring cycle: 150 ms measurement cycle as true rms value
Threshold adjustment voltage: 2...20 % of Un selected
Repeat accuracy: +/- 0.5 % for input circuit; +/- 3 % for time delay
Setting accuracy of the switching threshold: +/- (1.5 % + 1 V)
Measurement error: < 0.05 %/Hz with frequency variation; < 0.05 %/°C with temperature variation
Response time: <= 300 ms
Insulation resistance: > 100 MOhm at 500 V DC conforming to IEC 60255-27
[Ui] rated insulation voltage: 400 V
[Uimp] rated impulse withstand voltage: 4 kV during 1.2/50 µs
Dielectric test voltage: 2.5 kV, 1 min AC 50 Hz conforming to IEC 60255-27
Mounting position: Any position
Connections - terminals: Screw terminals, 2 x 0.5...2 x 2.5 mm² (AWG 20...AWG 14) solid without cable end; Screw terminals, 2 x 0.5...2 x 1.5 mm² (AWG 20...AWG 16) flexible with cable end; Screw terminals, 1 x 0.5...1 x 3.3 mm² (AWG 20...AWG 12) solid without cable end; Screw terminals, 1 x 0.5...1 x 2.5 mm² (AWG 20...AWG 14) flexible with cable end
Tightening torque: 0.6…1 N.m conforming to IEC 60947-1; 0.60…0.99 N.m conforming to IEC 60947-1
Housing material: Self-extinguishing plastic
Local signalling: LED Un: (steady), green for power ON; LED R1: (steady), amber for relay energised; LED R1: (blinking), amber for timing in progress; LED R2: (steady), amber for relay energised; LED R2: (blinking), amber for timing in progress; LED PL: (steady), red for alarm phase failure triggered; LED PS: (blinking), red for alarm phase sequence failure triggered; LED UV: (steady), red for alarm undervoltage failure triggered; LED OV: (blinking), red for alarm overvoltage failure triggered; LED UF: (steady), red for alarm underfrequency failure triggered; LED OF: (blinking), red for alarm overfrequency failure triggered; LED ASYM: (steady), red for alarm asymmentry failure triggered
Mounting support: 35 mm DIN rail conforming to IEC 60715
Electrical durability: 100000 cycles
Mechanical durability: 10000000 cycles
Utilisation category: AC-15 conforming to IEC 60947-5-1; DC-13 conforming to IEC 60947-5-1; AC-1 conforming to IEC 60947-4-1; DC-1 conforming to IEC 60947-4-1
[Ith] conventional free air thermal current: 8 A
Contacts material: Cadmium free
Width: 22.5 mm
height: 90 mm
Depth: 99 mm
Contacts type and composition: 2 C/O
Net weight: 0.125 kg
Environment
Immunity to microbreaks: 10 ms
Electromagnetic compatibility: Voltage dips and interruptions immunity test - test level: 70 % (25/30 cycles) conforming to IEC 61000-4-11; Electrostatic discharge - test level: 6 kV level 3 (contact discharge) conforming to IEC 61000-4-2; Radiated radio-frequency electromagnetic field immunity test - test level: 10 V/m level 3 conforming to IEC 61000-4-3; Immunity for industrial environments conforming to IEC 61000-6-2; 1 MHz damped oscillating wave - test level: 2.5 kV CM, 1 kV DM criteria B conforming to IEC 61000-4-18; Voltage dips and interruptions immunity test - test level: 0 % (0.5...25 cycles) conforming to IEC 61000-4-11; Magnetic field at power frequency - test level: 30 A/m (continuous)-300 A/m (1-3 s) level 4 conforming to IEC 61000-4-8; Surge immunity test - test level: 2 kV level 4 (differential mode) conforming to IEC 61000-4-5; Immunity for residential, commercial and light-industrial environments conforming to IEC 61000-6-1; Voltage dips and interruptions immunity test - test level: 40 % (10/12 cycles) conforming to IEC 61000-4-11; Voltage interruptions - test level: 0 % criteria C (250/300 cycles) conforming to IEC 61000-4-29; Electrical fast transient/burst immunity test - test level: 4 kV criteria B (direct) conforming to IEC 61000-4-4; Emission standard for industrial environments conforming to IEC 61000-6-4; Surge immunity test - test level: 4 kV level 4 (common mode) conforming to IEC 61000-4-5; Electrostatic discharge - test level: 8 kV level 3 (air discharge) conforming to IEC 61000-4-2; Conducted RF disturbances level 3 conforming to IEC 61000-4-6
Standards: IEC 60255-1
product certifications: CE; UL; CSA; CCC; EAC; RCM
Directives: 2014/30/EU - electromagnetic compatibility; 2014/35/EU - low voltage directive; 2014/53/EU - radio equipment directive
Ambient air temperature for storage: -40…70 °C
Ambient air temperature for operation: -20…60 °C
Relative humidity: 93…97 % at 25…55 °C conforming to IEC 60068-2-30
Vibration resistance: 0.075 mm (f= 10…58.1 Hz) not in operation conforming to IEC 60068-2-6; 1 gn (f= 58.1…150 Hz) not in operation conforming to IEC 60068-2-6; 0.035 mm (f= 10…58.1 Hz) in operation conforming to IEC 60068-2-6; 0.5 gn (f= 58.1…150 Hz) in operation conforming to IEC 60068-2-6
Shock resistance: 15 gn (duration = 11 ms) for not in operation conforming to IEC 60068-2-27; 5 gn (duration = 11 ms) for in operation conforming to IEC 60068-2-27
IP degree of protection: IP20 (terminals) conforming to IEC 60529; IP40 (housing) conforming to IEC 60529; IP40 (front panel) conforming to IEC 60529
Pollution degree: 3 conforming to IEC 60664-1; 3 conforming to UL 508
Overvoltage category: III conforming to IEC 60664-1; III conforming to UL 508
Packing Units
Unit Type of Package 1: PCE
Number of Units in Package 1: 1
Package 1 Height: 9.6 cm
Package 1 Width: 2.5 cm
Package 1 Length: 10.8 cm
Package 1 Weight: 136.0 g
Unit Type of Package 2: S02
Number of Units in Package 2: 36
Package 2 Height: 15 cm
Package 2 Width: 30 cm
Package 2 Length: 40 cm
Package 2 Weight: 5.578 kg
Unit Type of Package 3: P06
Number of Units in Package 3: 576
Package 3 Height: 75 cm
Package 3 Width: 60 cm
Package 3 Length: 80 cm
Package 3 Weight: 98 kg
Offer Sustainability
Sustainable offer status: Green Premium product
REACh Regulation: Reference contains Substances of Very High Concern above the threshold
EU RoHS Directive: Pro-active compliance (Product out of EU RoHS legal scope)
Mercury free: Yes
China RoHS Regulation: X
RoHS exemption information: Yes
Environmental Disclosure: ENVPEP1504008EN
Circularity Profile: ENVEOLI1504008EN
WEEE: The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
© 2018 Alplan Kft.