Skip to main content

Schneider-Electric
NSYCUX1K2R

ClimaSys standard cooling unit roof of enclosure - 1150W at 230 V
Barcode: 3606480654008
Tariff code:

This product is discontinued.

Please contact us for possible replacement product options.

Link to the manufacturers site: NSYCUX1K2R - ClimaSys standard cooling unit roof of enclosure - 1150W at 230 V

Main

range: ClimaSys

product name: CU

product or component type: Cooling unit

mounting location: Roof of enclosure

type of installation: Indoor

product destination: For enclosure

mounting mode: By screws

input voltage: 230 V 50/60 Hz

network number of phases: 1 phase

cooling power: 1150 W 50/60 Hz L35-L35; 900 W 50/60 Hz L35-L50

Complementary

height: 415 mm

width: 567 mm

depth: 401 mm

[In] rated current: 3.2 A

inrush current: 11 A

power consumption in W: 550 W at 50/60 Hz, L35-L35; 660 W at 50/60 Hz, L35-L50

energy efficiency ratio: 2.1

control type: Electronic controller

temperature setting range: 20…55 °C at 50 Hz; 20…50 °C at 60 Hz

ambient air temperature for operation: 20…46 °C inside the enclosure: ; 55 °C maximum: ; 20…55 °C at 50 Hz outside the enclosure: ; 20…50 °C at 60 Hz outside the enclosure:

noise level: 65 dB conforming to EN/ISO 3746

pressure: 25 bar

air flow: Internal circuit: 570 m3/h at 50/60 Hz; External circuit: 1010 m3/h at 50/60 Hz

net weight: 40 kg

cooling gas type: R134a (0.63 kg)

type of ventilation filter: Optional external circuit filter

protection type: Thermal protection: T 6 A; Short-circuit protection (magnetic):

material: Stainless steel

colour: Grey (RAL 7035)

Environment

product certifications: CE

directives: 2006/42/EC - machinery; 2004/108/EC - electromagnetic compatibility; 2006/95/EC - low voltage directive

standards: EN 60204-1; EN 60335-2-40; EN/ISO 12100; EN 60335-1; EN 378

IP degree of protection: IP34 conforming to IEC 60529 (on the external circuit); IP54 conforming to IEC 60529 (on the internal circuit)

Offer Sustainability

REACh Regulation: Free of Substances of Very High Concern above the threshold

REACh free of SVHC: Yes

EU RoHS Directive: Compliant

Toxic heavy metal free: Yes

Mercury free: Yes

RoHS exemption information: Yes

China RoHS Regulation:  Pro-active China RoHS declaration (out of China RoHS legal scope)

WEEE: The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins

© 2018 Alplan Kft.