Schneider-Electric
LV563321
Tariff code: 8536209090
Link to the manufacturers site: LV563321 - EasyPact CVS630N (50 kA) 4P4D TM500D
Main
Range: EasyPact
Range of product: EasyPact CVS400...630
product name: EasyPact CVS
Device short name: CVS630N
Product or component type: Circuit breaker
Device application: Distribution
Poles description: 4P
Protected poles description: 4D
Earth-leakage protection: Without
[In] rated current: 500 A at 40 °C
Network type: AC
Utilisation category: Category A
Breaking capacity: 70 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2; 50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2; 42 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
Trip unit name: TM-D
Trip unit technology: Thermal-magnetic
Trip unit rating: 500 A at 40 °C
Protection type: Short-circuit protection (magnetic); Overload protection (thermal)
Complementary
[Uimp] rated impulse withstand voltage: 8 kV conforming to EN/IEC 60947-2
Network frequency: 50/60 Hz
Breaking capacity code: N
[Ics] rated service breaking capacity: 70 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2; 50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2; 32 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
Neutral position: Left
Mechanical durability: 15000 cycles
Electrical durability: 4000 cycles 415 V In conforming to IEC 60947-2
Control type: Toggle
Thermal protection adjustment range: 350…500 A
Neutral protection setting: 1 x Ir (4D)
Long time pick-up adjustment type Ir: Adjustable
Long time pick-up adjustment range: 0.7...1 x In
Long time delay adjustment type: Fixed
Instantaneous pick-up adjustment type Ii: Adjustable
Instantaneous pick-up adjustment range: 5...10 x In
Contact position indicator: Yes
Mounting support: Backplate
Mounting mode: Fixed
Upside connection: Front
Downside connection: Front
Connections - terminals: Screw connection
Connection pitch: 45 mm
Compatibility code: CVS630
Width: 185 mm
Depth: 110 mm
Height: 255 mm
Net weight: 7.1 kg
Environment
Standards: IEC 60947-2; EN 60947-2
Product certifications: IEC; GOST
Electrical shock protection class: Class II
Pollution degree: 3 conforming to IEC 60664-1
IP degree of protection: IP40
Ambient air temperature for operation: -25…70 °C
Ambient air temperature for storage: -50…85 °C
Packing Units
Unit Type of Package 1: PCE
Number of Units in Package 1: 1
Package 1 Height: 15.500 cm
Package 1 Width: 20.300 cm
Package 1 Length: 29.500 cm
Package 1 Weight: 7.048 kg
Unit Type of Package 2: S03
Number of Units in Package 2: 2
Package 2 Height: 30.000 cm
Package 2 Width: 30.000 cm
Package 2 Length: 40.000 cm
Package 2 Weight: 14.584 kg
Unit Type of Package 3: P06
Number of Units in Package 3: 16
Package 3 Height: 75.000 cm
Package 3 Width: 60.000 cm
Package 3 Length: 80.000 cm
Package 3 Weight: 134.624 kg
Offer Sustainability
REACh Regulation: Reference contains Substances of Very High Concern above the threshold
EU RoHS Directive: Compliant with Exemptions
Environmental Disclosure: ENVPEP2211039
Circularity Profile: ENVEOLI2211039
WEEE: The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
PVC free: Yes
Take-back: No
Carbon footprint (kg.eq.CO2 per CR, Total Life cycle) : 2540
© 2018 Alplan Kft.