Skip to main content

Schneider-Electric
LV540524

EasyPact CVS400N 3P 50kA komplett megszakító ETS2.3 400 3P3D kioldóval és VIGI MB modullal
Barcode: 3606480249228
Tariff code: 8536209090

This product is discontinued.

Please contact us for possible replacement product options.

Link to the manufacturers site: LV540524 - EasyPact CVS400N 3P 50kA komplett megszakító ETS2.3 400 3P3D kioldóval és VIGI MB modullal

Main

Range: EasyPact

Range of produc: EasyPact CVS400...630

Product name: EasyPact CVS

Device short name: Vigi CVS400N

Product or component type: Earth leakage circuit breaker

Device application: Distribution

Poles description: 3P

Protected poles description: 3D

earth-leakage protection: With

[In] rated current: 400 A at 40 °C

Network type: AC

utilisation category: Category A

Breaking capacity: 70 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2; 50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2; 42 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2

Trip unit name: ETS 2.3

Trip unit technology: Electronic

Trip unit rating: 400 A at 40 °C

Protection type: Overload protection (long time); Instantaneous short-circuit protection; Short time short-circuit protection

Complementary

[Uimp] rated impulse withstand voltage: 8 kV conforming to EN/IEC 60947-2

Network frequency: 50/60 Hz

Breaking capacity code: N

[Ics] rated service breaking capacity: 70 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2; 50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2; 32 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2

Mechanical durability: 15000 cycles

Electrical durability: 6000 cycles 415 V In conforming to IEC 60947-2

Trip unit protection functions: LSoI

control type: Toggle

Long time pick-up adjustment type Ir: Adjustable 9 settings

Long time pick-up adjustment range: 160…400 A

Long time delay adjustment type: Fixed

[tr] long-time delay adjustment range: 5.5 s at 7.2 x Ir; 8 s at 6 x Ir; 200 s at 1.5 x Ir

thermal memory: Yes

Short-time pick-up adjustment type Isd: Adjustable 9 settings

[Isd] short-time pick-up adjustment range: 1.5...10 x Ir

Short-time delay adjustment type: Fixed

Instantaneous pick-up adjustment type Ii: Fixed

instantaneous pick-up adjustment range: 11 x In

earth-leakage add-on module name: MB

Earth-leakage protection class: Class A

Residual earth-leakage sensitity adjustment type: Adjustable 5 settings

[IΔn] residual earth-leakage sensitive adjustment: 0.3 A; 1 A; 3 A; 10 A; 30 A

Residual earth-leakage time delay adjustment type: Adjustable 4 settings

[Δt] residual earth-leakage time delay adjustment: 0 ms 40 ms; 60 ms 140 ms; 150 ms 300 ms; 310 ms 800 ms

Contact position indicator: Yes

Mounting mode: Fixed

mounting support: Backplate

Upside connection: Front

downside connection: Front

Connections - terminals: Screw connection

Connection pitch: 45 mm

Compatibility code: CVS400

Width: 140 mm

Depth: 110 mm

height: 355 mm

Net weight: 4.7 kg

Environment

Standards: EN 60947-2; IEC 60947-2

product certifications: GOST; IEC

Electrical shock protection class: Class II

Pollution degree: 3 conforming to IEC 60664-1

IP degree of protection: IP40

ambient air temperature for operation: -25…70 °C

Ambient air temperature for storage: -50…85 °C

Packing Units

Unit Type of Package 1: PCE

Number of Units in Package 1: 1

Package 1 Height: 24.4 cm

Package 1 Width: 16.0 cm

Package 1 Length: 30.0 cm

Package 1 Weight: 6.039 kg

Offer Sustainability

Sustainable offer status: Green Premium product

REACh Regulation: Reference contains Substances of Very High Concern above the threshold

EU RoHS Directive: Compliant with Exemptions

Mercury free: Yes

China RoHS Regulation: Product out of China RoHS scope. Substance declaration for your information

RoHS exemption information: Yes

Environmental Disclosure: ENVPEP1603002EN

Circularity Profile: ENVEOLI1603002EN

WEEE: The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins