Skip to main content

Schneider-Electric
LV480864

ISFL400 direct 185mm busbar screws M12 - fuse switch-disconnector
Net discounted price 838.41 EUR
Available when ordered (delivery time: 8 working day(s))
Barcode: 3606480341229
Tariff code: 8536508090

Link to the manufacturers site: LV480864 - ISFL400 direct 185mm busbar screws M12 - fuse switch-disconnector

Main

Range: FuPacT

Product name: FuPacT ISFL

Device short name: ISFL400

Product or component type: Fuse-switch disconnector

Device application: Equipment protection, monitoring and control; Distribution

Signalling function: Integrated fuse monitor

Poles description: 1 x 3P switchable

Number of fuse carriers: 3

Fuse type: DIN

Fuse size: NH2

Suitability for isolation: Yes conforming to EN/IEC 60947-3

Visible break: Yes

Contact position indicator: Yes

[Ith] conventional free air thermal current: 400 A ( 40 °C ) power dissipation per fuse: 34 W

[Ithe] conventional enclosed thermal current: 400 A at 40 °C, Power dissipation per fuse: 34 W

maximum power dissipation per pole: 53 W

[Ue] rated operational voltage: 690 V AC 50/60 Hz; 800 V AC 50/60 Hz AC-20; 800 V DC DC-20

[Ui] rated insulation voltage: 1000 V AC 50/60 Hz; 1000 V DC

[Uimp] rated impulse withstand voltage: 8 kV

[Ie] rated operational current: AC-21B: 400 A at 220/240 V AC 50/60 Hz; AC-21B: 400 A at 380/415 V AC 50/60 Hz; AC-21B: 400 A at 440/480 V AC 50/60 Hz; AC-21B: 400 A at 500 V AC 50/60 Hz; AC-21B: 400 A at 660/690 V AC 50/60 Hz; AC-22B: 400 A at 220/240 V AC 50/60 Hz; AC-22B: 400 A at 380/415 V AC 50/60 Hz; AC-22B: 400 A at 440/480 V AC 50/60 Hz; AC-22B: 400 A at 500 V AC 50/60 Hz; AC-23B: 400 A at 220/240 V AC 50/60 Hz; AC-23B: 400 A at 380/415 V AC 50/60 Hz

Complementary

Breaking capacity: 120 kA at 415 V (AC); 120 kA at 500 V (AC); 120 kA at 690 V (AC)

[Icw] rated short-time withstand current: 15 kA for 1 s

[Im] rated making and breaking capacity: 30 kA at 690 V

Rated duty: Uninterrupted

control type: Fuse carriers handle

Provision for padlocking: 3 padlocks

Mounting position: Vertical

Mounting mode: Fixed

Mounting support: Busbars

Mounting location: One above the other

contact operation: Single-break

Mechanical durability: 800 cycles

Electrical durability: AC-21B: 200 cycles 690 V AC 50/60 Hz; AC-22B: 200 cycles 500 V AC 50/60 Hz; AC-23B: 200 cycles 415 V AC 50/60 Hz

Connections - terminals: Screw connection downstream M12 400 A; Direct connection upstream 400 A 185 mm

Tightening torque: 40 N.m

Width: 100 mm

height: 741 mm

Depth: 190 mm

Net weight: 5 kg

Standards: EN/IEC 60947-1; EN/IEC 60947-3

product certifications: CE; CCC; EAC

Environment

Electrical shock protection class: Class II front face

IP degree of protection: IP20 conforming to IEC 60529

IK degree of protection: IK07 conforming to EN 50102

Pollution degree: 3 conforming to IEC 60947

ambient air temperature for operation: -20…70 °C

Ambient air temperature for storage: -50…85 °C

Compatibility code: Fuse_monitor_ISFL400

Packing Units

Unit Type of Package 1: PCE

Number of Units in Package 1: 1

Package 1 Height: 11.400 cm

Package 1 Width: 23.300 cm

Package 1 Length: 78.800 cm

Package 1 Weight: 5.650 kg

Unit Type of Package 2: P12

Number of Units in Package 2: 30

Package 2 Height: 117.000 cm

Package 2 Width: 80.000 cm

Package 2 Length: 120.000 cm

Package 2 Weight: 178.560 kg

Offer Sustainability

Sustainable offer status: Green Premium product

REACh Regulation: Free of Substances of Very High Concern above the threshold

REACh free of SVHC: Yes

EU RoHS Directive: Compliant

Toxic heavy metal free: Yes

Mercury free: Yes

China RoHS Regulation:  Pro-active China RoHS declaration (out of China RoHS legal scope)

RoHS exemption information: Yes

Environmental Disclosure: ENVPEP1701003EN

Circularity Profile: N/A

© 2018 Alplan Kft.