Schneider-Electric
LV480512
Tariff code: 8536508090
This product is discontinued.
There is a replacement product available.
Link to the manufacturers site: LV480512 - switch-disconnector fuse, Fupact INFD800, 3 poles, DIN (3), 800 A, front control
Main
range of product: INF200...800
range: FuPact
product name: Fupact INF
device short name: INFD800
product or component type: Switch-disconnector-fuse
device application: Protection
poles description: 3P
protected poles description: 3f
fuse type: DIN
fuse size: NH3
network type: AC; DC
network frequency: 50/60 Hz
Complementary
control type: Operating shaft (without handle)
rotary handle mounting location: Front
mounting mode: Fixed
mounting support: Mounting plate
[Ie] rated operational current: AC-22A: 800 A AC 50/60 Hz 220/240 V; AC-22A: 800 A AC 50/60 Hz 380/415 V; AC-22A: 800 A AC 50/60 Hz 440/480 V; AC-22A: 800 A AC 50/60 Hz 500/525 V; AC-22A: 800 A AC 50/60 Hz 660/690 V; DC-22A: 800 A DC 250 V 2 poles in series; DC-23A: 800 A DC 250 V 2 poles in series; AC-22A: 800 A AC 50/60 Hz 480 V conforming to NEMA; AC-23A: 800 A AC 50/60 Hz 220/240 V; AC-23A: 800 A AC 50/60 Hz 380/415 V; AC-23A: 800 A AC 50/60 Hz 440/480 V; AC-23A: 800 A AC 50/60 Hz 480 V conforming to NEMA; AC-23A: 800 A AC 50/60 Hz 500/525 V; AC-23A: 800 A AC 50/60 Hz 660/690 V; DC-22A: 720 A DC 500 V 3 poles in series; DC-22A: 800 A DC 125 V 1 pole; DC-23A: 720 A DC 500 V 3 poles in series; DC-23A: 800 A DC 125 V 1 pole
[Ith] conventional free air thermal current: 800 A ( 40 °C ) power dissipation per fuse: 65 W vertical; 509 A ( 70 °C ) horizontal; 544 A ( 65 °C ) horizontal; 566 A ( 70 °C ) vertical; 577 A ( 60 °C ) horizontal; 605 A ( 65 °C ) vertical; 609 A ( 55 °C ) horizontal; 638 A ( 50 °C ) horizontal; 641 A ( 60 °C ) vertical; 667 A ( 45 °C ) horizontal; 676 A ( 55 °C ) vertical; 694 A ( 40 °C ) horizontal; 709 A ( 50 °C ) vertical; 720 A ( 35 °C ) horizontal; 741 A ( 45 °C ) vertical
[Ithe] conventional enclosed thermal current: 720 A at 40 °C, Power dissipation per fuse: 55 W (800 mm x 1000 mm x 330 mm); 800 A at 40 °C, Power dissipation per fuse: 65 W
maximum power: AC-23: 250 kW at 220/240 V AC 50/60 Hz; AC-23: 450 kW at 380/400 V AC 50/60 Hz; AC-23: 450 kW at 415 V AC 50/60 Hz; AC-23: 560 kW at 500/525 V AC 50/60 Hz; AC-23: 710 kW at 660/690 V AC 50/60 Hz
rated duty: Uninterrupted
[Ui] rated insulation voltage: 1000 V AC 50/60 Hz; 1000 V DC
[Uimp] rated impulse withstand voltage: 12 kV
[Ue] rated operational voltage: 690 V AC 50/60 Hz; 1000 V AC 50/60 Hz AC-20; 1000 V DC DC-20; 750 V DC
[Im] rated making and breaking capacity: Icm 220 kA at 500 V conforming to DIN (with fuse); Icn 100 kA at 500 V conforming to DIN (with fuse); Icm 176 kA at 415 V conforming to DIN (with fuse); Icm 176 kA at 690 V conforming to DIN (with fuse); Icn 80 kA at 415 V conforming to DIN (with fuse); Icn 80 kA at 690 V conforming to DIN (with fuse); Icm 55 kA at 690 V (without fuse); Icm 77 kA at 415 V (without fuse); Icm 83 kA at 500 V (without fuse)
suitability for isolation: Yes conforming to IEC 60947-1
contact position indicator: Yes
contact operation: Double-break
Environment
mechanical durability: 5000 cycles
electrical durability: AC-22A: 500 cycles 500 V AC 50/60 Hz; AC-22A: 500 cycles 690 V AC 50/60 Hz; AC-23A: 500 cycles 500 V AC 50/60 Hz; AC-23A: 500 cycles 690 V AC 50/60 Hz
[Icw] rated short-time withstand current: 20 kA for 1 s; 4 kA for 30 s; 5 kA for 20 s; 11.6 kA for 3 s
design: Horizontal design
connections terminals: Screw connection
connections - terminals: Screw connection M12 800 A
tightening torque: 50...75 N.m for terminal
height: 306 mm
width: 341 mm
depth: 233 mm
standards: EN/IEC 60947-3; EN/IEC 60947-1
IP degree of protection: IP20 fuse compartment:
pollution degree: 3
compatibility code: INF200...800
Offer Sustainability
Sustainable offer status: Green Premium product
REACh Regulation: Free of Substances of Very High Concern above the threshold
REACh free of SVHC: Yes
EU RoHS Directive: Compliant
Toxic heavy metal free: Yes
Mercury free: Yes
RoHS exemption information: Yes
China RoHS Regulation: Pro-active China RoHS declaration (out of China RoHS legal scope)
Environmental Disclosure: ENVPEP110102EN
WEEE: The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
PVC free: Yes