Schneider-Electric
LR9D02
Tariff code: 8536490099
Link to the manufacturers site: LR9D02 - TeSys LRD - electronic thermal overload relay - 3P - 0.4...2 A
Main
Range: TeSys
Product name: TeSys LRD
Device short name: LR9D
product or component type: Electronic thermal overload relay
Relay application: Motor protection
Product compatibility: LC1D25; LC1D09; LC1D32; LC1D38; LC1D18; LC1D12
Thermal overload class: Class 5…30
Thermal protection adjustment range: 0.4…2 A
Power consumption in W: 300 mW
Mounting support: Under contactor; Plate, with specific accessories; Rail, with specific accessories
Complementary
[Ue] rated operational voltage: 690 V for power circuit; 660 V for signalling circuit
[Ui] rated insulation voltage: Power circuit: 1000 V; Signalling circuit: 690 V
Tripping threshold: 1.25 In conforming to IEC 60947-4-1
Control type: Red push-button: stop and manual reset; White 2 microswitches: adjustable trip class; Red knob: automatic reset; White dial: full-load current adjustment
Time range: 1.5...4 min - automatic reset time
[Ith] conventional free air thermal current: 5 A for signalling circuit
Associated fuse rating: 5 A gG for signalling circuit; 5 A BS for signalling circuit
[Uimp] rated impulse withstand voltage: 6 kV
Phase failure sensitivity: Phase difference > 40% 3 s conforming to IEC 60947-4-1
Electromagnetic compatibility: Surge withstand: 2 kV common mode conforming to IEC 61000-4-5; Resistance to electrostatic discharge: 8 kV conforming to IEC 61000-4-2; Immunity to radiated radio-electrical interference: 10 V/m conforming to IEC 61000-4-3; Immunity to fast transients: 2 kV conforming to IEC 61000-4-4
Connections - terminals: Control circuit: screw clamp terminals 1 cable 2.5 mm² - cable stiffness: solid or flexible - without cable end; Power circuit: screw clamp terminals 1 cable 16 mm² - cable stiffness: solid or flexible - without cable end
Tightening torque: Control circuit: 0.8 N.m on screw clamp terminals; Power circuit: 3.1 N.m on screw clamp terminals
Height: 72.5 mm
Width: 45 mm
Depth: 79.9 mm
Net weight: 0.18 kg
Environment
Standards: EN/IEC 60947-4-1; EN/IEC 60947-5-1; UL 60947-4-1; UL 60947-5-1; CSA C22.2 No 60947-4-1; CSA C22.2 No 60947-5-1; GB/T 14048.4; GB/T 14048.5
Product certifications: IECEE CB Scheme; UL; CSA; CCC
IP degree of protection: IP20 front face conforming to IEC 60529
Ambient air temperature for operation: -25…70 °C conforming to IEC 60255-8
Ambient air temperature for storage: -55…80 °C
Operating altitude: 2000 m without derating
Mechanical robustness: Vibrations 10...150 Hz: 6 Gn conforming to IEC 60068-2-6; Shocks 11 ms: 15 gn conforming to IEC 60068-2-7
Dielectric strength: 6 kV 50 Hz conforming to IEC 60255-5
Packing Units
Unit Type of Package 1: PCE
Number of Units in Package 1: 1
Package 1 Height: 5.5 cm
Package 1 Width: 7.5 cm
Package 1 Length: 9.2 cm
Package 1 Weight: 207.0 g
Unit Type of Package 2: S02
Number of Units in Package 2: 30
Package 2 Height: 15.0 cm
Package 2 Width: 30.0 cm
Package 2 Length: 40.0 cm
Package 2 Weight: 6.544 kg
Unit Type of Package 3: P06
Number of Units in Package 3: 480
Package 3 Height: 50.0 cm
Package 3 Width: 80.0 cm
Package 3 Length: 60.0 cm
Package 3 Weight: 121.86 kg
Offer Sustainability
REACh Regulation: Reference contains Substances of Very High Concern above the threshold
EU RoHS Directive: Compliant with Exemptions
Mercury free: Yes
China RoHS Regulation: Product out of China RoHS scope. Substance declaration for your information
RoHS exemption information: Yes
Environmental Disclosure: N/A
Circularity Profile: N/A
WEEE: The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins