Schneider-Electric
LR2D3563
Tariff code: 8536490099
Link to the manufacturers site: LR2D3563 - TeSys LRD thermal overload relays - 63...80 A - class 20
Main
Range: TeSys
Product name: TeSys LRD; TeSys Deca
product or component type: Differential thermal overload relay
Device short name: LR2D
Relay application: Motor protection
Product compatibility: LC1D95; LC1D80
Network type: AC; DC
Thermal overload class: Class 20 conforming to IEC 60947-4-1
Thermal protection adjustment range: 63…80 A
[Ui] rated insulation voltage: Power circuit: 600 V conforming to CSA; Power circuit: 600 V conforming to UL; Power circuit: 690 V conforming to IEC 60947-4-1
Complementary
Network frequency: 0...400 Hz
Mounting support: Plate, with specific accessories; Rail, with specific accessories; Under contactor
Tripping threshold: 1.14 +/- 0.06 Ir conforming to IEC 60947-4-1
Auxiliary contact composition: 1 NO + 1 NC
[Ith] conventional free air thermal current: 5 A for signalling circuit
Permissible current: 0.72 A at 500 V AC-15 for signalling circuit; 0.06 A at 440 V DC-13 for signalling circuit
[Ue] rated operational voltage: 1000 V AC 0...400 Hz for power circuit conforming to IEC 60947-4-1
Associated fuse rating: 4 A gG for signalling circuit; 4 A BS for signalling circuit
[Uimp] rated impulse withstand voltage: 6 kV
Phase failure sensitivity: Tripping current 130 % of Ir on two phase, the last one at 0
Control type: Red push-button: stop; Blue push-button: reset
Temperature compensation: -20…60 °C
Connections - terminals: Power circuit: screw clamp terminals 1 cable(s) 4…35 mm² flexible without cable end; Power circuit: screw clamp terminals 1 cable(s) 4…35 mm² flexible with cable end; Power circuit: screw clamp terminals 1 cable(s) 4…35 mm² solid without cable end; Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm² flexible without cable end; Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm² flexible with cable end; Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm² solid without cable end
Tightening torque: Control circuit: 1.7 N.m - on screw clamp terminals; Power circuit: 9 N.m - on screw clamp terminals
Height: 100 mm
Width: 75 mm
Depth: 121 mm
Net weight: 0.535 kg
Compatibility code: LR2D
Environment
Climatic withstand: conforming to IACS E10
IP degree of protection: IP20 conforming to IEC 60529
Ambient air temperature for operation: -20…60 °C without derating conforming to IEC 60947-4-1
Ambient air temperature for storage: -60…70 °C
Flame retardance: V1 conforming to UL 94
Mechanical robustness: Vibrations: 6 Gn conforming to IEC 60068-2-6; Shocks: 15 Gn for 11 ms conforming to IEC 60068-2-7
Dielectric strength: 2.2 kV at 50 Hz conforming to IEC 60947-1
Standards: EN/IEC 60947-4-1; EN/IEC 60947-5-1; UL 60947-4-1; UL 60947-5-1; CSA C22.2 No 60947-4-1; CSA C22.2 No 60947-5-1
Product certifications: IEC; UL; CSA; EAC; DNV-GL; LROS (Lloyds register of shipping); UKCA
Packing Units
Unit Type of Package 1: PCE
Number of Units in Package 1: 1
Package 1 Height: 7.700 cm
Package 1 Width: 8.500 cm
Package 1 Length: 11.800 cm
Package 1 Weight: 534.000 g
Unit Type of Package 2: S02
Number of Units in Package 2: 12
Package 2 Height: 15.000 cm
Package 2 Width: 30.000 cm
Package 2 Length: 40.000 cm
Package 2 Weight: 6.737 kg
Offer Sustainability
Sustainable offer status: Green Premium product
REACh Regulation: Free of Substances of Very High Concern above the threshold
REACh free of SVHC: Yes
EU RoHS Directive: Compliant
Toxic heavy metal free: Yes
Mercury free: Yes
China RoHS Regulation: Pro-active China RoHS declaration (out of China RoHS legal scope)
RoHS exemption information: Yes
Environmental Disclosure: ENVPEP110101EN
Circularity Profile: ENVEOLI1101001
WEEE: The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
© 2018 Alplan Kft.