Schneider-Electric
LC1D38BD
Tariff code: 8536419089
Link to the manufacturers site: LC1D38BD - TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 38 A - 24 V DC standard coil
Main
Range: TeSys; TeSys Deca
Range of product: TeSys Deca
Product or component type: Contactor
Device short name: LC1D
Contactor application: Resistive load; Motor control
Utilisation category: AC-4; AC-1; AC-3; AC-3e
Poles description: 3P
[Ue] rated operational voltage: Power circuit: <= 690 V AC 25...400 Hz; Power circuit: <= 300 V DC
[Ie] rated operational current: 50 A (at <60 °C) at <= 440 V AC AC-1 for power circuit; 38 A (at <60 °C) at <= 440 V AC AC-3 for power circuit; 38 A (at <60 °C) at <= 440 V AC AC-3e for power circuit
[Uc] control circuit voltage: 24 V DC
Complementary
Motor power kW: 18.5 kW at 500 V AC 50/60 Hz (AC-3); 18.5 kW at 660...690 V AC 50/60 Hz (AC-3); 7.5 kW at 400 V AC 50/60 Hz (AC-4); 18.5 kW at 380...400 V AC 50/60 Hz (AC-3); 9 kW at 220...230 V AC 50/60 Hz (AC-3); 18.5 kW at 415...440 V AC 50/60 Hz (AC-3); 18.5 kW at 500 V AC 50/60 Hz (AC-3e); 18.5 kW at 660...690 V AC 50/60 Hz (AC-3e); 18.5 kW at 380...400 V AC 50/60 Hz (AC-3e); 9 kW at 220...230 V AC 50/60 Hz (AC-3e); 18.5 kW at 415...440 V AC 50/60 Hz (AC-3e)
Motor power hp: 10 hp at 230/240 V AC 50/60 Hz for 3 phases motors; 10 hp at 200/208 V AC 50/60 Hz for 3 phases motors; 5 hp at 240 V AC 50/60 Hz for 1 phase motors; 20 hp at 480 V AC 50/60 Hz for 3 phases motors; 25 hp at 600 V AC 50/60 Hz for 3 phases motors
Compatibility code: LC1D
Pole contact composition: 3 NO
Protective cover: With
[Ith] conventional free air thermal current: 10 A (at 60 °C) for signalling circuit; 50 A (at 60 °C) for power circuit
Irms rated making capacity: 140 A AC for signalling circuit conforming to IEC 60947-5-1; 250 A DC for signalling circuit conforming to IEC 60947-5-1; 550 A at 440 V for power circuit conforming to IEC 60947
Rated breaking capacity: 550 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current: 60 A 40 °C - 10 min for power circuit; 430 A 40 °C - 1 s for power circuit; 150 A 40 °C - 1 min for power circuit; 310 A 40 °C - 10 s for power circuit; 100 A - 1 s for signalling circuit; 120 A - 500 ms for signalling circuit; 140 A - 100 ms for signalling circuit
Associated fuse rating: 10 A gG for signalling circuit conforming to IEC 60947-5-1; 63 A gG at <= 690 V coordination type 1 for power circuit; 63 A gG at <= 690 V coordination type 2 for power circuit
Average impedance: 2 mOhm - Ith 50 A 50 Hz for power circuit
Power dissipation per pole: 5 W AC-1; 3 W AC-3; 3 W AC-3e
[Ui] rated insulation voltage: Power circuit: 600 V CSA certified; Power circuit: 600 V UL certified; Signalling circuit: 690 V conforming to IEC 60947-1; Signalling circuit: 600 V CSA certified; Signalling circuit: 600 V UL certified; Power circuit: 690 V conforming to IEC 60947-4-1
Overvoltage category: III
Pollution degree: 3
[Uimp] rated impulse withstand voltage: 6 kV conforming to IEC 60947
Safety reliability level: B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1; B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
Mechanical durability: 30 Mcycles
Electrical durability: 1.4 Mcycles 50 A AC-1 at Ue <= 440 V; 1.4 Mcycles 38 A AC-3 at Ue <= 440 V; 1.4 Mcycles 38 A AC-3e at Ue <= 440 V
Control circuit type: DC standard
Coil technology: Built-in bidirectional peak limiting diode suppressor
Control circuit voltage limits: 0.1...0.25 Uc (-40…70 °C):drop-out DC; 0.7...1.25 Uc (-40…60 °C):operational DC; 1...1.25 Uc (60…70 °C):operational DC
Inrush power in W: 5.4 W (at 20 °C)
Hold-in power consumption in W: 5.4 W at 20 °C
Operating time: 20 ±20 % ms opening; 63 ±15 % ms closing
Time constant: 28 ms
Maximum operating rate: 3600 cyc/h 60 °C
Connections - terminals: Control circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with cable end; Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible without cable end; Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: flexible without cable end; Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible with cable end; Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: solid without cable end; Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: solid without cable end; Power circuit: screw clamp terminals 1 2.5…10 mm² - cable stiffness: flexible without cable end; Power circuit: screw clamp terminals 2 2.5…10 mm² - cable stiffness: flexible without cable end; Power circuit: screw clamp terminals 1 1…10 mm² - cable stiffness: flexible with cable end; Power circuit: screw clamp terminals 2 1.5…6 mm² - cable stiffness: flexible with cable end; Power circuit: screw clamp terminals 1 1.5…10 mm² - cable stiffness: solid without cable end; Power circuit: screw clamp terminals 2 2.5…10 mm² - cable stiffness: solid without cable end
Tightening torque: Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm; Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2; Power circuit: 2.5 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm; Power circuit: 2.5 N.m - on screw clamp terminals - with screwdriver Philips No 2; Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver pozidriv No 2; Power circuit: 2.5 N.m - on screw clamp terminals - with screwdriver pozidriv No 2
Auxiliary contact composition: 1 NO + 1 NC
Auxiliary contacts type: type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1; type mirror contact 1 NC conforming to IEC 60947-4-1
Signalling circuit frequency: 25...400 Hz
Minimum switching voltage: 17 V for signalling circuit
Minimum switching current: 5 mA for signalling circuit
Insulation resistance: > 10 MOhm for signalling circuit
Non-overlap time: 1.5 ms on de-energisation between NC and NO contact; 1.5 ms on energisation between NC and NO contact
Mounting support: Plate; Rail
Contact compatibility: M4
Environment
Standards: CSA C22.2 No 14; EN 60947-4-1; EN 60947-5-1; IEC 60947-4-1; IEC 60947-5-1; UL 60947-4-1; IEC 60335-1:Clause 30.2; IEC 60335-2-40:Annex JJ; UL 60335-2-40:Annex JJ; CSA C22.2 No 60947-4-1
Product certifications: UL; CCC; CSA; Marine; UKCA; EAC; CB Scheme
IP degree of protection: IP20 front face conforming to IEC 60529
Protective treatment: TH conforming to IEC 60068-2-30
Climatic withstand: conforming to IACS E10 exposure to damp heat; conforming to IEC 60947-1 Annex Q category D exposure to damp heat
Permissible ambient air temperature around the device: -40…60 °C; 60…70 °C with derating
Operating altitude: 0...3000 m
Fire resistance: 850 °C conforming to IEC 60695-2-1
Flame retardance: V1 conforming to UL 94
Mechanical robustness: Vibrations contactor open (2 Gn, 5...300 Hz) ; Vibrations contactor closed (4 Gn, 5...300 Hz) ; Shocks contactor closed (15 Gn for 11 ms) ; Shocks contactor open (8 Gn for 11 ms)
Height: 85 mm
Width: 45 mm
Depth: 101 mm
Net weight: 0.54 kg
Packing Units
Unit Type of Package 1: PCE
Number of Units in Package 1: 1
Package 1 Height: 5.000 cm
Package 1 Width: 9.000 cm
Package 1 Length: 11.000 cm
Package 1 Weight: 590.000 g
Unit Type of Package 2: S02
Number of Units in Package 2: 15
Package 2 Height: 15.000 cm
Package 2 Width: 30.000 cm
Package 2 Length: 40.000 cm
Package 2 Weight: 8.959 kg
Unit Type of Package 3: P06
Number of Units in Package 3: 240
Package 3 Height: 75.000 cm
Package 3 Width: 60.000 cm
Package 3 Length: 80.000 cm
Package 3 Weight: 153.296 kg
Offer Sustainability
Sustainable offer status: Green Premium product
REACh Regulation: Reference contains Substances of Very High Concern above the threshold
EU RoHS Directive: Compliant with Exemptions
Mercury free: Yes
China RoHS Regulation: Product out of China RoHS scope. Substance declaration for your information
RoHS exemption information: Yes
Environmental Disclosure: ENVPEP110230EN
Circularity Profile: ENVEOLI1102030EN
© 2018 Alplan Kft.