Skip to main content

Schneider-Electric
LC1D383P7

contactor TeSys LC1-D - 3 poles - AC-3 440V 38 A - coil 230 V AC
Net discounted price 158.58 EUR
Available when ordered (delivery time: 11 working day(s))
Barcode: 3389110805444
Tariff code: 8536490099

Link to the manufacturers site: LC1D383P7 - contactor TeSys LC1-D - 3 poles - AC-3 440V 38 A - coil 230 V AC

Main

Range: TeSys; TeSys Deca

Range of produc: TeSys Deca

Product or component type: Contactor

Device short name: LC1D

contactor application: Resistive load; Motor control

utilisation category: AC-3; AC-1; AC-3e

Poles description: 3P

[Ue] rated operational voltage: Power circuit: <= 690 V AC 25...400 Hz

[Ie] rated operational current: 50 A (at <60 °C) at <= 440 V AC AC-1 for power circuit; 38 A (at <60 °C) at <= 440 V AC AC-3 for power circuit; 38 A (at <60 °C) at <= 440 V AC AC-3e for power circuit

[Uc] control circuit voltage: 230 V AC 50/60 Hz

Complementary

Motor power kW: 18.5 kW at 500 V AC 50/60 Hz (AC-3); 18.5 kW at 660...690 V AC 50/60 Hz (AC-3); 7.5 kW at 400 V AC 50/60 Hz (AC-4); 18.5 kW at 380...400 V AC 50/60 Hz (AC-3); 18.5 kW at 415...440 V AC 50/60 Hz (AC-3); 9 kW at 220...230 V AC 50/60 Hz (AC-3); 18.5 kW at 500 V AC 50/60 Hz (AC-3e); 18.5 kW at 660...690 V AC 50/60 Hz (AC-3e); 18.5 kW at 380...400 V AC 50/60 Hz (AC-3e); 18.5 kW at 415...440 V AC 50/60 Hz (AC-3e); 9 kW at 220...230 V AC 50/60 Hz (AC-3e)

Compatibility code: LC1D

Pole contact composition: 3 NO

Protective cover: With

[Ith] conventional free air thermal current: 10 A (at 60 °C) for control circuit; 50 A (at 60 °C) for power circuit

Irms rated making capacity: 140 A AC for control circuit conforming to IEC 60947-5-1; 250 A at 440 V for power circuit conforming to IEC 60947

Rated breaking capacity: 550 A at 440 V for power circuit conforming to IEC 60947

Associated fuse rating: 10 A gG for control circuit conforming to IEC 60947-5-1; 63 A gG at <= 690 V coordination type 1 for power circuit; 63 A gG at <= 690 V coordination type 2 for power circuit

Average impedance: 2 mOhm - Ith 50 A 50 Hz for power circuit

Power dissipation per pole: 3 W AC-3; 5 W AC-1; 3 W AC-3e

[Ui] rated insulation voltage: Control circuit: 600 V CSA certified; Control circuit: 600 V UL certified; Power circuit: 600 V CSA certified; Power circuit: 600 V UL certified; Control circuit: 690 V conforming to IEC 60947-1; Power circuit: 690 V conforming to IEC 60947-1

Overvoltage category: III

[Uimp] rated impulse withstand voltage: 6 kV conforming to IEC 60947

Safety reliability level: B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1; B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1

Mechanical durability: 15000000 cycles

Control circuit type: AC at 50/60 Hz

Coil technology: Without built-in bidirectional peak limiting diode suppressor

Control circuit voltage limits: 0.3...0.6 Uc (60 °C):drop-out AC 50/60 Hz; 0.8...1.1 Uc (60 °C):operational AC 50 Hz; 0.85...1.1 Uc (60 °C):operational AC 60 Hz

Inrush power in VA: 70 VA cos phi 0.75 (at 20 °C)

Hold-in power consumption in VA: 7 VA 50 Hz cos phi 0.3 (at 20 °C); 7.5 VA 60 Hz cos phi 0.3 (at 20 °C)

Heat dissipation: 2…3 W at 50/60 Hz for control circuit

Operating time: 4...19 ms opening; 12...22 ms closing

Maximum operating rate: 3600 cyc/h 60 °C

Connections - terminals: Control circuit: spring terminal 1 4 mm² - cable stiffness: flexible without cable end; Control circuit: spring terminal 2 4 mm² - cable stiffness: flexible without cable end; Power circuit: spring terminal 1 4 mm² - cable stiffness: flexible without cable end; Power circuit: spring terminal 2 4 mm² - cable stiffness: flexible without cable end

Auxiliary contact composition: 1 NO + 1 NC

Auxiliary contacts type: type mirror contact 1 NC conforming to IEC 60947-4-1; type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1

Minimum switching voltage: 17 V for control circuit

Minimum switching current: 5 mA for control circuit

Insulation resistance: > 10 MOhm for control circuit

Non-overlap time: 1.5 ms on de-energisation between NC and NO contacts; 1.5 ms on energisation between NC and NO contacts

mounting support: Rail; Plate

Environment

Standards: EN 60947-5-1; EN 60947-4-1; CSA C22.2 No 14; IEC 60947-4-1; IEC 60947-5-1; UL 508; IEC 60335-1

product certifications: LROS (Lloyds register of shipping); DNV; RINA; GOST; UL; CSA; CCC; GL; BV; UKCA

IP degree of protection: IP2X conforming to IEC 60529; IP2X conforming to VDE 0106

Climatic withstand: conforming to IACS E10 exposure to damp heat; conforming to IEC 60947-1 Annex Q category D exposure to damp heat

Permissible ambient air temperature around the device: -5…60 °C; -40…70 °C at Uc

Operating altitude: 3000 m without derating

Fire resistance: 850 °C conforming to IEC 60695-2-1

Flame retardance: V1 conforming to UL 94

Mechanical robustness: Shocks contactor closed (15 Gn for 11 ms) ; Shocks contactor opened (8 Gn for 11 ms) ; Vibrations contactor opened (2 Gn, 5...300 Hz) ; Vibrations contactor closed (4 Gn, 5...300 Hz)

height: 85 mm

Width: 45 mm

Depth: 92 mm

Net weight: 0.38 kg

Packing Units

Unit Type of Package 1: PCE

Number of Units in Package 1: 1

Package 1 Height: 11.4 cm

Package 1 Width: 10.5 cm

Package 1 Length: 5.4 cm

Package 1 Weight: 375.0 g

Offer Sustainability

Sustainable offer status: Green Premium product

REACh Regulation: Free of Substances of Very High Concern above the threshold

REACh free of SVHC: Yes

EU RoHS Directive: Compliant

Toxic heavy metal free: Yes

Mercury free: Yes

China RoHS Regulation:  Pro-active China RoHS declaration (out of China RoHS legal scope)

RoHS exemption information: Yes

Environmental Disclosure: ENVPEP110229EN

Circularity Profile: ENVEOLI110229EN

WEEE: The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins

PVC free: Yes

© 2018 Alplan Kft.