Skip to main content

Schneider-Electric
EZC250N3200

circuit breaker Easypact EZC250N - TMD - 200 A - 3 poles 3d
Net discounted price 253.26 EUR
In stock: 1 pc(s)
Barcode: 3303431999866
Tariff code: 8536209090

Link to the manufacturers site: EZC250N3200 - circuit breaker Easypact EZC250N - TMD - 200 A - 3 poles 3d

Main

Range: EasyPact

Range of produc: EasyPact

Product name: EasyPact EZC

Product or component type: Circuit breaker

Device short name: Easypact EZC250N

circuit breaker name: Easypact EZC250N

Device application: Distribution

Poles description: 3P

Protected poles description: 3t

Network type: DC; AC

Network frequency: 50/60 Hz

[In] rated current: 200 A at 40 °C

[Ui] rated insulation voltage: 690 V AC 50/60 Hz conforming to IEC 60947-2

[Uimp] rated impulse withstand voltage: 6 kV conforming to IEC 60947-2

[Ue] rated operational voltage: 550 V AC 50/60 Hz conforming to IEC 60947-2; 250 V DC conforming to IEC 60947-2

Breaking capacity code: N

Breaking capacity: 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2; 50 kA Icu at 110...130 V AC 50/60 Hz conforming to IEC 60947-2; 50 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2; 20 kA Icu at 125 V DC 1P conforming to IEC 60947-2; 20 kA Icu at 250 V DC 2P conforming to IEC 60947-2; 25 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2; 25 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2; 8 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2

[Ics] rated service breaking capacity: 10 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2; 25 kA at 110/130 V AC 50/60 Hz conforming to IEC 60947-2; 10 kA at 125 V DC conforming to IEC 60947-2; 10 kA at 250 V DC conforming to IEC 60947-2; 25 kA at 220/230/240 V AC 50/60 Hz conforming to IEC 60947-2; 4 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2; 12.5 kA at 380 V AC 50/60 Hz conforming to IEC 60947-2; 12.5 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2

Suitability for isolation: Yes conforming to IEC 60947-2

utilisation category: Category A

Trip unit name: TM-D

Trip unit technology: Thermal-magnetic

Trip unit rating: 200 A at 50 °C

Protection type: Overload protection; Short-circuit protection

Pollution degree: 3 conforming to IEC 60664-1; 3 conforming to IEC 947-1

Complementary

control type: Toggle

Mounting mode: Fixed

mounting support: Backplate

Upside connection: Front

downside connection: Front

Mechanical durability: 10000 cycles

Electrical durability: Category A: 5000 cycles 415 V AC 50/60 Hz conforming to IEC 60947-2

Connection pitch: 35 mm

local signalling: Positive contact indication

Neutral protection setting: Without protection

earth-leakage protection: Without

height: 165 mm

Width: 105 mm

Depth: 60 mm

Market segment: Small commercial

Compatibility code: EZC250

Environment

Standards: EN/IEC 60947-1; GB/T 14048.2; EN/IEC 60947-2

IP degree of protection: IP20 conforming to IEC 60529

IK degree of protection: IK07 conforming to IEC 62262

ambient air temperature for operation: -25…70 °C

Ambient air temperature for storage: -35…85 °C

Packing Units

Unit Type of Package 1: PCE

Number of Units in Package 1: 1

Package 1 Height: 10.5 cm

Package 1 Width: 11.5 cm

Package 1 Length: 18.0 cm

Package 1 Weight: 1.57 kg

Unit Type of Package 2: S03

Number of Units in Package 2: 8

Package 2 Height: 30 cm

Package 2 Width: 30 cm

Package 2 Length: 40 cm

Package 2 Weight: 12.94 kg

Unit Type of Package 3: P12

Number of Units in Package 3: 64

Package 3 Height: 50 cm

Package 3 Width: 80 cm

Package 3 Length: 120 cm

Package 3 Weight: 120.86 kg

Offer Sustainability

Sustainable offer status: Green Premium product

REACh Regulation: Free of Substances of Very High Concern above the threshold

REACh free of SVHC: Yes

EU RoHS Directive: Compliant with Exemptions

RoHS exemption information: Yes

Environmental Disclosure: ENVPEP2312021

Circularity Profile: N/A

WEEE: The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins