Skip to main content

Schneider-Electric
EZC100H1016

circuit breaker Easypact EZC100H - TMD - 16 A - 1 pole 1d
Net discounted price 88.74 EUR
Available when ordered (delivery time: 8 working day(s))
Barcode: 3303431120239
Tariff code: 8536201090

Link to the manufacturers site: EZC100H1016 - circuit breaker Easypact EZC100H - TMD - 16 A - 1 pole 1d

Main

Range: EasyPact

Range of produc: EasyPact

Product name: EasyPact EZC

Product or component type: Circuit breaker

Device short name: Easypact EZC100H

circuit breaker name: Easypact EZC100H

Device application: Distribution

Poles description: 1P

Protected poles description: 1t

Network type: DC; AC

Network frequency: 50/60 Hz

[In] rated current: 16 A at 40 °C

[Ui] rated insulation voltage: 690 V AC 50/60 Hz conforming to IEC 60947-2

[Uimp] rated impulse withstand voltage: 6 kV conforming to IEC 60947-2

[Ue] rated operational voltage: 125 V DC conforming to IEC 60947-2; 415 V AC 50/60 Hz conforming to IEC 60947-2

Breaking capacity code: H

Breaking capacity: 10 kA Icu at 125 V DC 1P conforming to IEC 60947-2; 25 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2; 50 kA Icu at 110...130 V AC 50/60 Hz conforming to IEC 60947-2; 5 kA Icu at 380...400 V AC 50/60 Hz conforming to IEC 60947-2; 5 kA Icu at 415 V AC 50/60 Hz conforming to IEC 60947-2

[Ics] rated service breaking capacity: 5 kA at 125 V DC conforming to IEC 60947-2; 12.5 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2; 25 kA at 110...130 V AC 50/60 Hz conforming to IEC 60947-2; 2.5 kA at 380...400 V AC 50/60 Hz conforming to IEC 60947-2; 2.5 kA at 415 V AC 50/60 Hz conforming to IEC 60947-2

Suitability for isolation: Yes conforming to IEC 60947-2

utilisation category: Category A

Trip unit name: TM-D

Trip unit technology: Thermal-magnetic

Trip unit rating: 16 A at 50 °C

Protection type: Overload protection; Short-circuit protection

Pollution degree: 3 conforming to IEC 60947

Complementary

control type: Toggle

Mounting mode: Fixed

mounting support: Backplate

Upside connection: Front

downside connection: Front

Mechanical durability: 8500 cycles

Electrical durability: Category A: 1500 cycles 415 V AC 50/60 Hz conforming to IEC 60947-2

Connection pitch: 25 mm

local signalling: Positive contact indication

Neutral protection setting: Without protection

earth-leakage protection: Without

height: 130 mm

Width: 25 mm

Depth: 60 mm

Market segment: Small commercial

Compatibility code: EZC100

Environment

Standards: JIS C8201-2-2; EN/IEC 60947-2; EN/IEC 60947-1; GB/T 14048.2

IP degree of protection: IP20 conforming to IEC 60529

IK degree of protection: IK07 conforming to EN 50102

ambient air temperature for operation: -25…70 °C

Ambient air temperature for storage: -35…85 °C

Packing Units

Unit Type of Package 1: PCE

Number of Units in Package 1: 1

Package 1 Height: 3 cm

Package 1 Width: 9.5 cm

Package 1 Length: 14 cm

Package 1 Weight: 349 g

Unit Type of Package 2: S02

Number of Units in Package 2: 32

Package 2 Height: 15 cm

Package 2 Width: 30 cm

Package 2 Length: 40 cm

Package 2 Weight: 11.41 kg

Unit Type of Package 3: P12

Number of Units in Package 3: 1024

Package 3 Height: 100 cm

Package 3 Width: 125 cm

Package 3 Length: 55 cm

Package 3 Weight: 382.376 kg

Offer Sustainability

Sustainable offer status: Green Premium product

REACh Regulation: Free of Substances of Very High Concern above the threshold

REACh free of SVHC: Yes

EU RoHS Directive: Compliant

Toxic heavy metal free: Yes

Mercury free: Yes

China RoHS Regulation: X

RoHS exemption information: Yes

Environmental Disclosure: ENVPEP1407009EN

Circularity Profile: N/A

WEEE: The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins