Skip to main content

Schneider-Electric
C63W36M500

circuit breaker ComPacT NSX630HB2, 100 kA at 690 VAC, MicroLogic 6.3 E-M trip unit 500 A, 3 poles 3d
Net discounted price 4,621.13 EUR
Available when ordered (delivery time: 13 working day(s))
Barcode: 3606481989284
Tariff code: 8536209090

Link to the manufacturers site: C63W36M500 - circuit breaker ComPacT NSX630HB2, 100 kA at 690 VAC, MicroLogic 6.3 E-M trip unit 500 A, 3 poles 3d

Main

Range: ComPacT new generation

Product name: ComPacT NSX new generation

Range of produc: ComPacT NSX400...630 new generation

Device short name: NSX630HB2

Product or component type: Circuit breaker

Device application: Motor protection

Poles description: 3P

Protected poles description: 3D

[In] rated current: 500 A at 65 °C

[Ue] rated operational voltage: 690 V AC 50/60 Hz

Network type: AC

Network frequency: 50/60 Hz

Suitability for isolation: Yes conforming to EN/IEC 60947-2

utilisation category: Category A

Breaking capacity: 100 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2; 100 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2; 100 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2

Breaking capacity code: HB2 100 kA 690 V AC

Trip unit name: MicroLogic 6.3 E-M

Trip unit technology: Electronic

Trip unit protection functions: LSIG

control type: Toggle

Mounting mode: Fixed

Complementary

[Ui] rated insulation voltage: 800 V AC 50/60 Hz

[Uimp] rated impulse withstand voltage: 8 kV

[Ics] rated service breaking capacity: 100 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2; 100 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2; 100 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2

Mechanical durability: 15000 cycles

Electrical durability: 8000 cycles at 440 V In/2; 4000 cycles at 440 V In; 6000 cycles at 690 V In/2; 2000 cycles at 690 V In

Power dissipation per pole: 25 W

mounting support: Backplate

Mounting position: Horizontal and vertical; Flat on the back

Upside connection: Front

downside connection: Front

Connection pitch: 45 mm

Protection type: L : for overload protection (long time); So : for short time short-circuit protection; I : for instantaneous short-circuit protection; G : for ground fault protection

Trip unit rating: 500 A at 65 °C

Motor tripping class: 10; 20; 30; 5

complementary motor protection: Stalled rotor; Protracted starting time; Phase unbalance; Underload

Long time pick-up adjustment type Ir: Adjustable 9 settings

Long time pick-up adjustment range: 250...500 A

Long time delay adjustment type: Adjustable

[tr] long-time delay adjustment range: 120 s at 1.5 x Ir for trip class 5; 6.5 s at 6 x Ir for trip class 5; 5 s at 7.2 x Ir for trip class 5; 240 s at 1.5 x Ir for trip class 10; 13.5 s at 6 x Ir for trip class 10; 10 s at 7.2 x Ir for trip class 10; 480 s at 1.5 x Ir for trip class 20; 26 s at 6 x Ir for trip class 20; 20 s at 7.2 x Ir for trip class 20; 720 s at 1.5 x Ir for trip class 30; 38 s at 6 x Ir for trip class 30; 30 s at 7.2 x Ir for trip class 30

thermal memory: 20 minutes before and after tripping

Short-time pick-up adjustment type Isd: Adjustable

[Isd] short-time pick-up adjustment range: 5...13 x Ir

Short-time delay adjustment type: Fixed

Instantaneous pick-up adjustment type Ii: Fixed

instantaneous pick-up adjustment range: 6500 A

ground-fault pick-up adjustment type: Adjustable 9 settings

[Ig] ground-fault pick-up adjustment range: 0.6...1 x In for In = 25 A; 0.3...1 x In for In = 50 A; 0.2...1 x In for In > 50 A; Ig enable on/off

ground-fault time delay adjustment type -tg: Adjustable 5 settings

[tg] Ground-fault time delay adjustment range: 0…0.4 s

earth-leakage protection: Without

Zone selective interlocking ZSI: With

Number of slots: 6 slot(s)

Local signalling: Flashing LED (green) for ready to operate; LED 95 % Ith (red) for temperature over set point

Display type: LCD display

Type of measurement: Energy meter

communication of data: Demand current and power; Protection and alarm settings; Maximeters/minimeters; Thermal image function; Phase sequence; Energy metering; Time-stamped histories and event tables; Maintenance indicators; Power quality; Instantaneous and demand values

Width: 140 mm

height: 255 mm

Depth: 110 mm

Net weight: 6.2 kg

Compatibility code: NSX630

Environment

Standards: EN/IEC 60947

product certifications: CCC; EAC; Marine

Overvoltage category: Class II

Electrical shock protection class: Class II

Pollution degree: 3 conforming to IEC 60664-1

IP degree of protection: IP40 conforming to IEC 60529

IK degree of protection: IK07 conforming to IEC 62262

ambient air temperature for operation: -25…70 °C

Ambient air temperature for storage: -40…85 °C

Relative humidity: 0…95 %

Operating altitude: 0...2000 m without derating; 2000 m...5000 m with derating

Packing Units

Unit Type of Package 1: PCE

Number of Units in Package 1: 1

Package 1 Height: 15.2 cm

Package 1 Width: 15.2 cm

Package 1 Length: 29.2 cm

Package 1 Weight: 5.81 kg

Offer Sustainability

Sustainable offer status: Green Premium product

REACh Regulation: Reference contains Substances of Very High Concern above the threshold

EU RoHS Directive: Compliant with Exemptions

Mercury free: Yes

China RoHS Regulation: Product out of China RoHS scope. Substance declaration for your information

RoHS exemption information: Yes

Environmental Disclosure: ENVPEP2309047EN

Circularity Profile: ENVEOLI2309047EN

PVC free: Yes

Halogen content performance: Halogen free plastic parts product

© 2018 Alplan Kft.