Skip to main content

Schneider-Electric
ATV71HU75M3Z

variable speed drive ATV71 - 7.5kW-10HP - 240V - EMC filter-w/o graphic terminal
Barcode: 3389118064430
Tariff code:

This product is discontinued.

Please contact us for possible replacement product options.

Link to the manufacturers site: ATV71HU75M3Z - variable speed drive ATV71 - 7.5kW-10HP - 240V - EMC filter-w/o graphic terminal

Main

range of product: Altivar 71

product or component type: Variable speed drive

product specific application: Complex, high-power machines

component name: ATV71

motor power kW: 7.5 kW, 3 phases at 200...240 V; 5.5 kW, single phase at 200...240 V

motor power hp: 10 hp, 3 phases at 200...240 V; 7.5 hp, single phase at 200...240 V

maximum motor cable length: 50 m shielded cable; 100 m unshielded cable

[Us] rated supply voltage: 200...240 V - 15...10 %

network number of phases: 3 phases; Single phase

line current: 39.4 A for 240 V 3 phases 7.5 kW / 10 hp; 40.1 A for 240 V single phase 5.5 kW / 7.5 hp; 45 A for 200 V 3 phases 7.5 kW / 10 hp; 47.3 A for 200 V single phase 5.5 kW / 7.5 hp

EMC filter: Integrated

assembly style: With heat sink

variant: Without remote graphic terminal

apparent power: 9.5 kVA at 240 V single phase 5.5 kW / 7.5 hp; 16.4 kVA at 240 V 3 phases 7.5 kW / 10 hp

prospective line Isc: 22 kA for 3 phases; 22 kA for single phase

nominal output current: 27.5 A at 4 kHz 230 V single phase 5.5 kW / 7.5 hp; 33 A at 4 kHz 230 V 3 phases 7.5 kW / 10 hp

maximum transient current: 41.3 A for 60 s single phase 5.5 kW / 7.5 hp; 45.3 A for 2 s single phase 5.5 kW / 7.5 hp; 49.5 A for 60 s 3 phases 7.5 kW / 10 hp; 54.5 A for 2 s 3 phases 7.5 kW / 10 hp

output frequency: 0.1…599 Hz

nominal switching frequency: 4 kHz

switching frequency: 1...16 kHz adjustable; 4...16 kHz with derating factor

asynchronous motor control profile: Voltage/frequency ratio (2 or 5 points); Sensorless flux vector control (SFVC) (voltage or current vector); ENA (Energy adaptation) system for unbalanced loads; Flux vector control (FVC) with sensor (current vector)

type of polarization: No impedance for Modbus

Complementary

product destination: Asynchronous motors; Synchronous motors

supply voltage limits: 170…264 V

supply frequency: 50...60 Hz - 5...5 %

network frequency: 47.5...63 Hz

speed range: 1…100 for asynchronous motor in open-loop mode, without speed feedback; 1…1000 for asynchronous motor in closed-loop mode with encoder feedback; 1…50 for synchronous motor in open-loop mode, without speed feedback

speed accuracy: +/- 0.01 % of nominal speed in closed-loop mode with encoder feedback 0.2 Tn to Tn; +/- 10 % of nominal slip without speed feedback 0.2 Tn to Tn

torque accuracy: +/- 15 % in open-loop mode, without speed feedback; +/- 5 % in closed-loop mode with encoder feedback

transient overtorque: 170 % of nominal motor torque +/- 10 % for 60 s every 10 minutes; 220 % of nominal motor torque +/- 10 % for 2 s

braking torque: <= 150 % with braking or hoist resistor; 30 % without braking resistor

synchronous motor control profile: Vector control without speed feedback

regulation loop: Adjustable PI regulator

motor slip compensation: Automatic whatever the load; Not available in voltage/frequency ratio (2 or 5 points); Adjustable; Suppressable

local signalling: 1 LED (red) for drive voltage

output voltage: <= power supply voltage

insulation: Electrical between power and control

type of cable: With a NEMA Type1 kit: 3 wire(s)UL 508 cable at 40 °C, copper 75 °C / PVC; With an IP21 or an IP31 kit: 3 wire(s)IEC cable at 40 °C, copper 70 °C / PVC; Without mounting kit: 1 wire(s)IEC cable at 45 °C, copper 70 °C / PVC; Without mounting kit: 1 wire(s)IEC cable at 45 °C, copper 90 °C / XLPE/EPR

electrical connection: Terminal, clamping capacity: 2.5 mm², AWG 14 (AI1-/AI1+, AI2, AO1, R1A, R1B, R1C, R2A, R2B, LI1...LI6, PWR); Terminal, clamping capacity: 16 mm², AWG 4 (L1/R, L2/S, L3/T, U/T1, V/T2, W/T3, PC/-, PO, PA/+, PA, PB)

tightening torque: 0.6 N.m (AI1-/AI1+, AI2, AO1, R1A, R1B, R1C, R2A, R2B, LI1...LI6, PWR); 3 N.m, 26.5 lb.in (L1/R, L2/S, L3/T, U/T1, V/T2, W/T3, PC/-, PO, PA/+, PA, PB)

supply: Internal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC +/- 5 %, <10 mA, protection type: overload and short-circuit protection; Internal supply: 24 V DC (21…27 V), <200 mA, protection type: overload and short-circuit protection

analogue input number: 2

analogue input type: AI1-/Al1+ bipolar differential voltage: +/- 10 V DC 24 V max, resolution 11 bits + sign; AI2 software-configurable current: 0...20 mA, impedance: 242 Ohm, resolution 11 bits; AI2 software-configurable voltage: 0...10 V DC 24 V max, impedance: 30000 Ohm, resolution 11 bits

sampling duration: 2 ms +/- 0.5 ms (AI1-/Al1+) - analog input(s); 2 ms +/- 0.5 ms (Al2) - analog input(s); 2 ms +/- 0.5 ms (LI1...LI5) - discrete input(s); 2 ms +/- 0.5 ms (LI6)if configured as logic input - discrete input(s)

response time: <= 100 ms in STO (Safe Torque Off); AO1 2 ms, tolerance +/- 0.5 ms for analog output(s); R1A, R1B, R1C 7 ms, tolerance +/- 0.5 ms for discrete output(s); R2A, R2B 7 ms, tolerance +/- 0.5 ms for discrete output(s)

accuracy: +/- 0.6 % (AI1-/Al1+) for a temperature variation 60 °C; +/- 0.6 % (AI2) for a temperature variation 60 °C; +/- 1 % (AO1) for a temperature variation 60 °C

linearity error: +/- 0.15 % of maximum value (AI1-/Al1+, AI2); +/- 0.2 % (AO1)

analogue output number: 1

analogue output type: AO1 software-configurable logic output 10 V 20 mA; AO1 software-configurable current 0...20 mA, impedance: 500 Ohm, resolution 10 bits; AO1 software-configurable voltage 0...10 V DC, impedance: 470 Ohm, resolution 10 bits

discrete output number: 2

discrete output type: Configurable relay logic: (R1A, R1B, R1C) NO/NC - 100000 cycles; Configurable relay logic: (R2A, R2B) NO - 100000 cycles

minimum switching current: 3 mA at 24 V DC for configurable relay logic

maximum switching current: R1, R2: 2 A at 250 V AC inductive load, cos phi = 0.4; R1, R2: 2 A at 30 V DC inductive load, cos phi = 0.4; R1, R2: 5 A at 250 V AC resistive load, cos phi = 1; R1, R2: 5 A at 30 V DC resistive load, cos phi = 1

discrete input number: 7

discrete input type: LI1...LI5: programmable 24 V DC with level 1 PLC, impedance: 3500 Ohm; LI6: switch-configurable 24 V DC with level 1 PLC, impedance: 3500 Ohm; LI6: switch-configurable PTC probe 0…6, impedance: 1500 Ohm; PWR: safety input 24 V DC, impedance: 1500 Ohm conforming to ISO 13849-1 level d

discrete input logic: Negative logic (sink) (LI1...LI5), > 16 V (state 0), < 10 V (state 1); Positive logic (source) (LI1...LI5), < 5 V (state 0), > 11 V (state 1); Negative logic (sink) (LI6)if configured as logic input, > 16 V (state 0), < 10 V (state 1); Positive logic (source) (LI6)if configured as logic input, < 5 V (state 0), > 11 V (state 1)

acceleration and deceleration ramps: Linear adjustable separately from 0.01 to 9000 s; S, U or customized; Automatic adaptation of ramp if braking capacity exceeded, by using resistor

braking to standstill: By DC injection

protection type: Against exceeding limit speed: drive; Against input phase loss: drive; Break on the control circuit: drive; Input phase breaks: drive; Line supply overvoltage: drive; Line supply undervoltage: drive; Overcurrent between output phases and earth: drive; Overheating protection: drive; Overvoltages on the DC bus: drive; Short-circuit between motor phases: drive; Thermal protection: drive; Motor phase break: motor; Power removal: motor; Thermal protection: motor

insulation resistance: > 1 mOhm 500 V DC for 1 minute to earth

frequency resolution: Analog input: 0.024/50 Hz; Display unit: 0.1 Hz

communication port protocol: Modbus; CANopen

connector type: 1 RJ45 (on front face) for Modbus; 1 RJ45 (on terminal) for Modbus; Male SUB-D 9 on RJ45 for CANopen

physical interface: 2-wire RS 485 for Modbus

transmission frame: RTU for Modbus

transmission rate: 4800 bps, 9600 bps, 19200 bps, 38.4 Kbps for Modbus on terminal; 9600 bps, 19200 bps for Modbus on front face; 20 kbps, 50 kbps, 125 kbps, 250 kbps, 500 kbps, 1 Mbps for CANopen

data format: 8 bits, 1 stop, even parity for Modbus on front face; 8 bits, odd even or no configurable parity for Modbus on terminal

number of addresses: 1…127 for CANopen; 1…247 for Modbus

method of access: Slave CANopen

marking: CE

operating position: Vertical +/- 10 degree

height: 295 mm

depth: 213 mm

width: 210 mm

net weight: 7 kg

option card: Communication card for CC-Link; Controller inside programmable card; Communication card for DeviceNet; Communication card for EtherNet/IP; Communication card for Fipio; I/O extension card; Communication card for Interbus-S; Interface card for encoder; Communication card for Modbus Plus; Communication card for Modbus TCP; Communication card for Modbus/Uni-Telway; Overhead crane card; Communication card for Profibus DP; Communication card for Profibus DP V1

Environment

noise level: 57.4 dB conforming to 86/188/EEC

dielectric strength: 2830 V DC between earth and power terminals; 4230 V DC between control and power terminals

electromagnetic compatibility: 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5; Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6; Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4; Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2; Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3; Voltage dips and interruptions immunity test conforming to IEC 61000-4-11

standards: UL Type 1; EN 61800-3 environments 1 category C3; IEC 60721-3-3 class 3S2; EN/IEC 61800-3; EN 61800-3 environments 2 category C3; EN 55011 class A group 2; IEC 60721-3-3 class 3C1; EN/IEC 61800-5-1

product certifications: GOST; UL; C-Tick; NOM 117; CSA

pollution degree: 2 conforming to EN/IEC 61800-5-1

IP degree of protection: IP20 on upper part without blanking plate on cover conforming to EN/IEC 60529; IP20 on upper part without blanking plate on cover conforming to EN/IEC 61800-5-1; IP21 conforming to EN/IEC 60529; IP21 conforming to EN/IEC 61800-5-1; IP41 on upper part conforming to EN/IEC 60529; IP41 on upper part conforming to EN/IEC 61800-5-1; IP54 on lower part conforming to EN/IEC 60529; IP54 on lower part conforming to EN/IEC 61800-5-1

vibration resistance: 1 gn (f= 13…200 Hz) conforming to EN/IEC 60068-2-6; 1.5 mm peak to peak (f= 3…13 Hz) conforming to EN/IEC 60068-2-6

shock resistance: 15 gn for 11 ms conforming to EN/IEC 60068-2-27

relative humidity: 5…95 % without condensation conforming to IEC 60068-2-3; 5…95 % without dripping water conforming to IEC 60068-2-3

ambient air temperature for operation: -10…50 °C (without derating)

ambient air temperature for storage: -25…70 °C

operating altitude: <= 1000 m without derating; 1000...3000 m with current derating 1 % per 100 m

Offer Sustainability

Sustainable offer status: Green Premium product

REACh Regulation: Free of Substances of Very High Concern above the threshold

EU RoHS Directive: Pro-active compliance (Product out of EU RoHS legal scope)

Mercury free: Yes

RoHS exemption information: Yes

China RoHS Regulation: X

Environmental Disclosure: ENVPEP050303EN

Circularity Profile: ENVEOLI100207EN

WEEE: The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins