Skip to main content

Schneider-Electric
ATV08PU09M2

ATV08 0,37 kW base plate with EMC - single phase
In stock: 2 pc(s)
Barcode: 3389110124248
Tariff code:

This product is discontinued.

This product is no longer manufactured, but we have it in stock. Please contact us for price and delivery information!

Link to the manufacturers site: ATV08PU09M2 - ATV08 0,37 kW base plate with EMC - single phase

Main

range of product: Altivar 08

product or component type: Variable speed drive

product specific application: Simple machine

component name: ATV08

assembly style: On base plate

EMC filter: Integrated

network number of phases: Single phase

[Us] rated supply voltage: 200...240 V +/- 10 %

supply frequency: 50...60 Hz - 5...5 %

motor power kW: 0.37 kW

line current: 5.3 A at 230 V, Isc = 1 kA

nominal output current: 2.1 A 4 kHz 230 V motor

maximum transient current: 3.1 A for 60 s

power dissipation in W: 20.5 W at nominal load

asynchronous motor control profile: Sensorless flux vector control with PWM type motor control signal

analogue input number: 1

Complementary

product destination: Asynchronous motors

built-in fan: Without

supply voltage limits: 180…264 V

network frequency limits: 47.5…63 Hz

speed drive output frequency: 0.5…200 Hz

nominal switching frequency: 4 kHz

switching frequency: 2...16 kHz adjustable; 4...16 kHz with derating factor

speed range: 1…10

transient overtorque: 150...170 % of nominal motor torque

regulation loop: Possible correction for machines with high resistive torque/inertia/fast cycles; Factory-set with the speed loop stability and gain; Adjustable frequency

motor slip compensation: Preset in factory; Adjustable

prospective line Isc: 1 kA

output voltage: <= power supply voltage

electrical connection: Control terminal 1.5 mm²; Power supply terminal 1.5 mm²

insulation: Galvanic insulation between power and control terminals

supply: Internal supply for logic inputs: 15 V 100 mA, protection type: overload and short-circuit protection; Internal supply for reference potentiometer (1 to 10 kOhm): 5 VDC 10 mA, protection type: overload and short-circuit protection

analogue input type: Configurable current AI1 4...20 mA 500 Ohm with load in parallel; Configurable voltage AI1 0...5 V 50000 Ohm; Configurable current AI1 0...20 mA 500 Ohm; Configurable voltage AI1 0...10 V 50000 Ohm

sampling duration: LI1...LI4: 20 ms discrete; AI1: 20 ms analog

linearity error: : +/- 1 % for output

discrete input number: 4

discrete input type: Assignable Ll1 forward 3500 Ohm 15 V 24 V; Assignable Ll2 reverse 3500 Ohm 15 V 24 V; Assignable Ll3/Ll4 4 preset speeds 3500 Ohm 15 V 24 V

discrete input logic: Positive logic (source) (LI1...LI4), < 5 V (state 0), > 11 V (state 1)

discrete output number: 2

discrete output type: Relay normally open R1 1 NO

minimum switching current: R1A, R1C 10 mA at 24 V DC

maximum switching current: 1.5 A 250 V AC inductive cos phi = 0.4 7 ms R1A, R1C; 1.5 A 30 V DC inductive cos phi = 0.4 7 ms R1A, R1C; 1.5 A 250 V AC resistive cos phi = 1 0 ms R1A, R1C; 1.5 A 30 V DC resistive cos phi = 1 0 ms R1A, R1C

acceleration and deceleration ramps: Linear from 0 to 99.9 s

braking to standstill: By DC injection

protection type: Line supply overvoltage: drive; Line supply undervoltage: drive; Overheating protection: drive; Short-circuit between motor phases: drive; Thermal protection: motor; Overcurrent between output phases and earth: drive

insulation resistance: > 500 MOhm

operating position: Vertical +/- 10 degree

CAD overall width: 72 mm

CAD overall height: 130 mm

CAD overall depth: 87 mm

Environment

electromagnetic compatibility: 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to EN/IEC 61000-4-5; Electrical fast transient/burst immunity test level 4 conforming to EN/IEC 61000-4-4; Electrostatic discharge immunity test level 3 conforming to EN/IEC 61000-4-2; Radiated radio-frequency electromagnetic field immunity test level 3 conforming to EN/IEC 61000-4-3; Conducted and radiated emissions conforming to EN 55011 class B; Conducted and radiated emissions conforming to IEC/EN 61800-3 environments 1 and 2

standards: EN/IEC 61800-3

product certifications: CSA; UL

marking: CE

IP degree of protection: IP20

relative humidity: 5…93 % without condensation conforming to IEC 60068-2-3; 5…93 % without dripping water conforming to IEC 60068-2-3

ambient air temperature for storage: -25…65 °C

ambient air temperature for operation: 0…40 °C without derating; 40…60 °C with current derating 2.2 % per °C

operating altitude: <= 1000 m without derating; > 1000 m with current derating 1 % per 100 m

© 2018 Alplan Kft.