Schneider-Electric
ATV08PU09M2
Tariff code:
This product is discontinued.
This product is no longer manufactured, but we have it in stock. Please contact us for price and delivery information!
Link to the manufacturers site: ATV08PU09M2 - ATV08 0,37 kW base plate with EMC - single phase
Main
range of product: Altivar 08
product or component type: Variable speed drive
product specific application: Simple machine
component name: ATV08
assembly style: On base plate
EMC filter: Integrated
network number of phases: Single phase
[Us] rated supply voltage: 200...240 V +/- 10 %
supply frequency: 50...60 Hz - 5...5 %
motor power kW: 0.37 kW
line current: 5.3 A at 230 V, Isc = 1 kA
nominal output current: 2.1 A 4 kHz 230 V motor
maximum transient current: 3.1 A for 60 s
power dissipation in W: 20.5 W at nominal load
asynchronous motor control profile: Sensorless flux vector control with PWM type motor control signal
analogue input number: 1
Complementary
product destination: Asynchronous motors
built-in fan: Without
supply voltage limits: 180…264 V
network frequency limits: 47.5…63 Hz
speed drive output frequency: 0.5…200 Hz
nominal switching frequency: 4 kHz
switching frequency: 2...16 kHz adjustable; 4...16 kHz with derating factor
speed range: 1…10
transient overtorque: 150...170 % of nominal motor torque
regulation loop: Possible correction for machines with high resistive torque/inertia/fast cycles; Factory-set with the speed loop stability and gain; Adjustable frequency
motor slip compensation: Preset in factory; Adjustable
prospective line Isc: 1 kA
output voltage: <= power supply voltage
electrical connection: Control terminal 1.5 mm²; Power supply terminal 1.5 mm²
insulation: Galvanic insulation between power and control terminals
supply: Internal supply for logic inputs: 15 V 100 mA, protection type: overload and short-circuit protection; Internal supply for reference potentiometer (1 to 10 kOhm): 5 VDC 10 mA, protection type: overload and short-circuit protection
analogue input type: Configurable current AI1 4...20 mA 500 Ohm with load in parallel; Configurable voltage AI1 0...5 V 50000 Ohm; Configurable current AI1 0...20 mA 500 Ohm; Configurable voltage AI1 0...10 V 50000 Ohm
sampling duration: LI1...LI4: 20 ms discrete; AI1: 20 ms analog
linearity error: : +/- 1 % for output
discrete input number: 4
discrete input type: Assignable Ll1 forward 3500 Ohm 15 V 24 V; Assignable Ll2 reverse 3500 Ohm 15 V 24 V; Assignable Ll3/Ll4 4 preset speeds 3500 Ohm 15 V 24 V
discrete input logic: Positive logic (source) (LI1...LI4), < 5 V (state 0), > 11 V (state 1)
discrete output number: 2
discrete output type: Relay normally open R1 1 NO
minimum switching current: R1A, R1C 10 mA at 24 V DC
maximum switching current: 1.5 A 250 V AC inductive cos phi = 0.4 7 ms R1A, R1C; 1.5 A 30 V DC inductive cos phi = 0.4 7 ms R1A, R1C; 1.5 A 250 V AC resistive cos phi = 1 0 ms R1A, R1C; 1.5 A 30 V DC resistive cos phi = 1 0 ms R1A, R1C
acceleration and deceleration ramps: Linear from 0 to 99.9 s
braking to standstill: By DC injection
protection type: Line supply overvoltage: drive; Line supply undervoltage: drive; Overheating protection: drive; Short-circuit between motor phases: drive; Thermal protection: motor; Overcurrent between output phases and earth: drive
insulation resistance: > 500 MOhm
operating position: Vertical +/- 10 degree
CAD overall width: 72 mm
CAD overall height: 130 mm
CAD overall depth: 87 mm
Environment
electromagnetic compatibility: 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to EN/IEC 61000-4-5; Electrical fast transient/burst immunity test level 4 conforming to EN/IEC 61000-4-4; Electrostatic discharge immunity test level 3 conforming to EN/IEC 61000-4-2; Radiated radio-frequency electromagnetic field immunity test level 3 conforming to EN/IEC 61000-4-3; Conducted and radiated emissions conforming to EN 55011 class B; Conducted and radiated emissions conforming to IEC/EN 61800-3 environments 1 and 2
standards: EN/IEC 61800-3
product certifications: CSA; UL
marking: CE
IP degree of protection: IP20
relative humidity: 5…93 % without condensation conforming to IEC 60068-2-3; 5…93 % without dripping water conforming to IEC 60068-2-3
ambient air temperature for storage: -25…65 °C
ambient air temperature for operation: 0…40 °C without derating; 40…60 °C with current derating 2.2 % per °C
operating altitude: <= 1000 m without derating; > 1000 m with current derating 1 % per 100 m
© 2018 Alplan Kft.