Schneider-Electric
ATS48C79Y
Tariff code:
This product is discontinued.
Please contact us for possible replacement product options.
Link to the manufacturers site: ATS48C79Y - soft starter for asynchronous motor - ATS48 - 720 A - 208..690 V - 220..710 KW
Main
range of product: Altistart 48
product or component type: Soft starter
product destination: Asynchronous motors
product specific application: Heavy duty industry and pumps
device short name: ATS48
[Us] rated supply voltage: 208...690 V - 15...10 %
motor power kW: 220 kW at 230 V for standard applications; 355 kW at 400 V for severe applications; 400 kW at 400 V for standard applications; 400 kW at 440 V for severe applications; 500 kW at 440 V for standard applications; 500 kW at 500 V for standard applications; 500 kW at 525 V for standard applications; 630 kW at 660 V for severe applications; 630 kW at 690 V for severe applications; 710 kW at 660 V for standard applications; 710 kW at 690 V for standard applications
motor power hp: 200 hp at 208 V for severe applications; 250 hp at 208 V for standard applications; 250 hp at 230 V for severe applications; 300 hp at 230 V for standard applications; 500 hp at 460 V for severe applications; 600 hp at 460 V for standard applications; 600 hp at 575 V for severe applications; 800 hp at 575 V for standard applications
power dissipation in W: 2073 W for standard applications; 2537 W for standard applications
utilisation category: AC-53A
type of start: Start with torque control (current limited to 5 In)
IcL starter rating: 790 A for connection in the motor supply line for standard applications; 790 A for connection in the motor supply line for severe applications
Complementary
assembly style: With heat sink
function available: External bypass (optional)
supply frequency: 50...60 Hz - 5...5 %
network frequency: 47.5...63 Hz
device connection: In the motor supply line
discrete output number: 2
discrete output type: (LO1) logic output 0 V common configurable; (LO2) logic output 0 V common configurable; (R1) relay outputs fault relay NO; (R2) relay outputs end of starting relay NO; (R3) relay outputs motor powered NO
output absolute accuracy precision: +/- 5 %
minimum switching current: 10 mA at 6 V DC for relay outputs
maximum switching current: Logic output 0.2 A at 30 V DC; Relay outputs 1.8 A at 230 V AC inductive load, cos phi = 0.5 20 ms; Relay outputs 1.8 A at 30 V DC inductive load, cos phi = 0.5 20 ms
discrete input number: 5
discrete input type: PTC, 750 Ohm at 25 °C; (Stop, Run, LI3, LI4) logic, <= 8 mA 4300 Ohm
discrete input voltage: 24 V <= 30 V
discrete input logic: Positive logic Stop, Run, LI3, LI4 at State 0: < 5 V and <= 2 mA at State 1: > 11 V, >= 5 mA
supply inrush current: 0.4...1.3 Icl adjustable
analogue output type: Current output AO: 0-20 mA or 4-20 mA, impedance <500 Ohm
communication port protocol: Modbus
connector type: 1 RJ45
communication data link: Serial
physical interface: RS485 multidrop
transmission rate: 4800, 9600 or 19200 bps
installed device: 31
protection type: Phase failure: line; Thermal protection: motor; Thermal protection: starter
marking: CE
operating position: Vertical +/- 10 degree
height: 890 mm
width: 770 mm
depth: 315 mm
net weight: 115 kg
power range: 110…220 kW at 200…240 V 3 phases; 250…500 kW at 380…440 V 3 phases; 250…500 kW at 480…500 V 3 phases
motor starter type: Soft starter
Environment
electromagnetic compatibility: Conducted and radiated emissions level A conforming to IEC 60947-4-2; Damped oscillating waves level 3 conforming to IEC 61000-4-12; Electrostatic discharge level 3 conforming to IEC 61000-4-2; Immunity to electrical transients level 4 conforming to IEC 61000-4-4; Immunity to radiated radio-electrical interference level 3 conforming to IEC 61000-4-3; Voltage/current impulse level 3 conforming to IEC 61000-4-5
standards: EN/IEC 60947-4-2
product certifications: CSA; UL; TCF; CCC; DNV; GOST; SEPRO; C-Tick; NOM 117
noise level: 60 dB
relative humidity: 0…95 % without condensation or dripping water conforming to EN/IEC 60068-2-3
ambient air temperature for operation: 40…60 °C (with current derating of 2 % per °C); -10…40 °C (without derating)
ambient air temperature for storage: -25…70 °C
operating altitude: <= 1000 m without derating; > 1000...2000 m with current derating of 2.2 % per additional 100 m
Offer Sustainability
Sustainable offer status: Green Premium product
REACh Regulation: Free of Substances of Very High Concern above the threshold
EU RoHS Directive: Pro-active compliance (Product out of EU RoHS legal scope)
Mercury free: Yes
RoHS exemption information: Yes
China RoHS Regulation: X
Environmental Disclosure: ENVPEP111033EN
Circularity Profile: ENVEOLI111009EN
WEEE: The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
© 2018 Alplan Kft.