Skip to main content

Schneider-Electric
ATS48C11Y

soft starter for asynchronous motor - ATS48 - 96 A - 208..690 V - 22..90 KW
Barcode: 3389110982343
Tariff code: 8537109899

This product is discontinued.

Please contact us for possible replacement product options.

Link to the manufacturers site: ATS48C11Y - soft starter for asynchronous motor - ATS48 - 96 A - 208..690 V - 22..90 KW

Main

range of product: Altistart 48

product or component type: Soft starter

product destination: Asynchronous motors

product specific application: Heavy duty industry and pumps

device short name: ATS48

utilisation category: AC-53A

[Us] rated supply voltage: 208...690 V - 15...10 %

supply frequency: 50...60 Hz - 5...5 %

motor power kW: 22 kW at 230 V for severe applications; 30 kW at 230 V for standard applications; 45 kW at 400 V for severe applications; 45 kW at 440 V for severe applications; 55 kW at 400 V for standard applications; 55 kW at 440 V for standard applications; 55 kW at 500 V for severe applications; 55 kW at 525 V for severe applications; 75 kW at 500 V for standard applications; 75 kW at 525 V for standard applications; 75 kW at 660 V for severe applications; 75 kW at 690 V for severe applications; 90 kW at 660 V for standard applications; 90 kW at 690 V for standard applications

motor power hp: 100 hp at 575 V for standard applications; 25 hp at 208 V for severe applications; 30 hp at 208 V for standard applications; 30 hp at 230 V for severe applications; 40 hp at 230 V for standard applications; 60 hp at 460 V for severe applications; 75 hp at 460 V for standard applications; 75 hp at 575 V for severe applications

Complementary

device connection: In the motor supply line

protection type: Phase failure: line; Thermal protection: motor; Thermal protection: starter

standards: EN/IEC 60947-4-2

product certifications: GOST; TCF; CCC; SEPRO; NOM 117; C-Tick; CSA; UL; DNV

marking: CE

discrete input number: 5

discrete input type: PTC, 750 Ohm at 25 °C; (Stop, Run, LI3, LI4) logic, <= 8 mA 4300 Ohm

discrete input logic: Positive logic Stop, Run, LI3, LI4 at State 0: < 5 V and <= 2 mA at State 1: > 11 V, >= 5 mA

minimum switching current: 10 mA at 6 V DC for relay outputs

discrete output number: 2

discrete output type: (LO1) logic output 0 V common configurable; (LO2) logic output 0 V common configurable; (R1) relay outputs fault relay NO; (R2) relay outputs end of starting relay NO; (R3) relay outputs motor powered NO

analogue output type: Current output AO: 0-20 mA or 4-20 mA, impedance <500 Ohm

communication port protocol: Modbus

connector type: 1 RJ45

communication data link: Serial

physical interface: RS485 multidrop

transmission rate: 4800, 9600 or 19200 bps

function available: External bypass (optional)

operating position: Vertical +/- 10 degree

height: 290 mm

width: 190 mm

depth: 235 mm

net weight: 8.3 kg

assembly style: With heat sink

installed device: 31

network frequency: 47.5...63 Hz

noise level: 58 dB

output absolute accuracy precision: +/- 5 %

type of start: Start with torque control (current limited to 5 In)

motor starter type: Soft starter

discrete input voltage: 24 V <= 30 V

IcL starter rating: 110 A for connection in the motor supply line for standard applications; 110 A for connection in the motor supply line for severe applications

power dissipation in W: 252 W for standard applications; 322 W for standard applications

power range: 15…25 kW at 200…240 V 3 phases; 30…50 kW at 200…240 V 3 phases; 55…100 kW at 380…440 V 3 phases; 55…100 kW at 480…500 V 3 phases

supply inrush current: 0.4...1.3 Icl adjustable

Environment

electromagnetic compatibility: Conducted and radiated emissions level A conforming to IEC 60947-4-2; Conducted and radiated emissions level B conforming to IEC 60947-4-2; Damped oscillating waves level 3 conforming to IEC 61000-4-12; Electrostatic discharge level 3 conforming to IEC 61000-4-2; Immunity to electrical transients level 4 conforming to IEC 61000-4-4; Immunity to radiated radio-electrical interference level 3 conforming to IEC 61000-4-3; Voltage/current impulse level 3 conforming to IEC 61000-4-5

relative humidity: 0…95 % without condensation or dripping water conforming to EN/IEC 60068-2-3

ambient air temperature for operation: 40…60 °C (with current derating of 2 % per °C); -10…40 °C (without derating)

ambient air temperature for storage: -25…70 °C

operating altitude: <= 1000 m without derating; > 1000...2000 m with current derating of 2.2 % per additional 100 m

Packing Units

Number of Units in Package 1: 1

Number of Units in Package 2: 2

Package 1 Height: 36.5 cm

Package 1 Length: 40 cm

Package 1 Weight: 10.657 kg

Package 1 Width: 30.5 cm

Package 2 Height: 73.5 cm

Package 2 Length: 60 cm

Package 2 Weight: 34.314 kg

Package 2 Width: 80 cm

Unit Type of Package 1: PCE

Unit Type of Package 2: P06

Offer Sustainability

Sustainable offer status: Green Premium product

REACh Regulation: Reference contains Substances of Very High Concern above the threshold

EU RoHS Directive: Pro-active compliance (Product out of EU RoHS legal scope)

Mercury free: Yes

RoHS exemption information: Yes

China RoHS Regulation: X

Environmental Disclosure: ENVPEP111031EN

Circularity Profile: ENVEOLI111007EN

WEEE: The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins

© 2018 Alplan Kft.