Schneider-Electric
A9MEM3565
Tariff code: 9028301900
Link to the manufacturers site: A9MEM3565 - iEM3555 energy meter - BACnet - 1 DI - 1 DO - multi-tariff - Rogowski coil
Main
Range: Acti9
Product name: Acti9 iEM3000
Device short name: iEM3565
Product or component type: Energy meter
Market segment: Buildings small building cost management: billing: main incomer; Buildings small building cost management: billing: sub feeder; Buildings small building cost management: billing: panelboard; Buildings medium building cost management: billing: main incomer; Buildings medium building cost management: billing: sub feeder; Buildings medium building cost management: billing: panelboard; Buildings large building cost management: billing: main incomer; Buildings large building cost management: billing: sub feeder; Buildings large building cost management: billing: panelboard; Buildings multi-site cost management: billing: main incomer; Buildings multi-site cost management: billing: sub feeder; Buildings multi-site cost management: billing: panelboard; Data center cost management: billing; Healthcare cost management: billing; Industry cost management: billing; Buildings small building cost management: cost allocation: main incomer; Buildings small building cost management: cost allocation: sub feeder; Buildings small building cost management: cost allocation: panelboard; Buildings medium building cost management: cost allocation: main incomer; Buildings medium building cost management: cost allocation: sub feeder; Buildings medium building cost management: cost allocation: panelboard; Buildings large building cost management: cost allocation: main incomer; Buildings large building cost management: cost allocation: sub feeder; Buildings large building cost management: cost allocation: panelboard; Buildings multi-site cost management: cost allocation: main incomer; Buildings multi-site cost management: cost allocation: sub feeder; Buildings multi-site cost management: cost allocation: panelboard; Data center cost management: cost allocation; Healthcare cost management: cost allocation; Industry cost management: cost allocation
Complementary
Poles description: 1P + N; 3P + N; 3P
Type of measurement: Active and reactive energy; Active and reactive power; Current; Voltage
Metering type: Active, reactive, apparent energy (signed, four quadrant)
Device application: Sub billing; Partial meter; Multi-tariff
Accuracy class: Class 0.5S active energy conforming to IEC 62053-22; Class 0.5S active energy conforming to ANSI C12.20
Analogue input type: Rogowski coil 50...5000 A
Rated voltage: 100…277 V +/- 20 %; 173…480 V +/- 20 %
Network frequency: 50 Hz; 60 Hz
Technology type: Electronic
Display type: LCD display
Sampling rate: 32 samples/cycle
Measurement current: 50…5000 A
Maximum value measured: 99999999.9 kWh; 99999999 MWh
Information displayed: Tariff (4)
Communication port protocol: BACnet at 9.6, 19.2, 38.4, 57.6, 76.8 kbauds
Communication port support: Screw terminal block: RS485
Local signalling: Green indicator light: power ON; Yellow flashing LED: accuracy checking; alarm: overload
Number of inputs: 1 digital 0...5 V/11...40 V 24 V DC
Number of outputs: 1 digital (static)
Output voltage: 5...40 V DC@50 mA
Mounting mode: Clip-on
mounting support: DIN rail
Connections - terminals: Current circuit: screw terminals 6 mm² cable(s) ; Voltage circuit: screw terminals 2.5 mm² cable(s) ; Input/output circuit: screw terminals 1.5 mm² cable(s) ; Communication: screw terminals 2.5 mm² cable(s)
Tightening torque: Input/output circuit: 0.5 N.m Philips screwdriver ; Voltage circuit: 0.5 N.m Philips screwdriver ; Current circuit: 0.8 N.m pozidriv screwdriver ; Communication: 0.5 N.m Philips screwdriver
Wire stripping length: Input/output circuit: 6 mm; Voltage circuit: 8 mm; Current circuit: 8 mm; Communication: 7 mm
Standards: BS EN 61326-1; IEC 61326-1; EN 61326-1; BS EN 61010-1:2010; EN 61010-1:2010; IEC 61010-1:2010; UL 61010-1:2010; BS EN 61010-2-30; IEC 61010-2-30; EN 61010-2-30; UL 61010-2-30; ANSI C12.20
Product certifications: CE conforming to IEC 61010-1 (safety); CE conforming to EN 61557-12 (power monitor); CE conforming to EN/IEC 61326-1 (EMC); UKCA conforming to BS EN 61010-1 (safety); UKCA conforming to BS EN 61557-12 (power monitor); UKCA conforming to BS EN 61326-1 (EMC); CULus conforming to UL 61010-1 (safety); CULus conforming to EN 61010-1 (safety); KZ; RCM
Compatibility code: IEM3565
Environment
IP degree of protection: IP40 front panel: conforming to IEC 60529; IP20 body: conforming to IEC 60529
IK degree of protection: IK08
Pollution degree: 2
Relative humidity: 5…95 % at 36 °C
Ambient air temperature for operation: -25…70 °C - IEC
Ambient air temperature for storage: -40…85 °C
Operating altitude: < 3000 m
Colour: White
9 mm pitches: 10
Width: 90 mm
height: 87 mm
Depth: 69 mm
Packing Units
Unit Type of Package 1: PCE
Number of Units in Package 1: 1
Package 1 Height: 8.8 cm
Package 1 Width: 9.8 cm
Package 1 Length: 10.5 cm
Package 1 Weight: 323 g
Unit Type of Package 2: S03
Number of Units in Package 2: 30
Package 2 Height: 30 cm
Package 2 Width: 30 cm
Package 2 Length: 40 cm
Package 2 Weight: 11.483 kg
Unit Type of Package 3: P06
Number of Units in Package 3: 240
Package 3 Height: 50 cm
Package 3 Width: 80 cm
Package 3 Length: 60 cm
Package 3 Weight: 100.364 kg
Offer Sustainability
Sustainable offer status: Green Premium product
REACh Regulation: Reference contains Substances of Very High Concern above the threshold
EU RoHS Directive: Compliant with Exemptions
Mercury free: Yes
China RoHS Regulation: X
RoHS exemption information: Yes
Environmental Disclosure: ENVPEP111276EN
Circularity Profile: ENVEOLI111261EN_V1
WEEE: The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
© 2018 Alplan Kft.