Skip to main content

Schneider-Electric
34403

circuit breaker Compact NS630bH - Micrologic 2.0 E - 630 A - 4 poles 4t
Barcode: 3606480344855
Tariff code:

This product is discontinued.

Please contact us for possible replacement product options.

Link to the manufacturers site: 34403 - circuit breaker Compact NS630bH - Micrologic 2.0 E - 630 A - 4 poles 4t

Main

range: ComPact

product name: ComPact NS

range of product: ComPact NS630b...1600

device short name: Compact NS630bH

product or component type: Circuit breaker

device application: Distribution

poles description: 4P

protected poles description: 4D

neutral position: Left

[In] rated current: 630 A at 50 °C

[Ue] rated operational voltage: 690 V AC 50/60 Hz

network type: AC

network frequency: 50/60 Hz

suitability for isolation: Yes conforming to EN/IEC 60947-2

utilisation category: Category B

breaking capacity: 42 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2; 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2; 70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2; 85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2; 50 kA Icu at 500/525 V AC 50/60 Hz conforming to IEC 60947-2

Breaking capacity code: H 70 kA 415 V AC

trip unit name: Micrologic 2.0 E

trip unit technology: Electronic

trip unit protection functions: LI

control type: Toggle; Rotary handle

mounting mode: Fixed

Complementary

[Ui] rated insulation voltage: 800 V AC 50/60 Hz conforming to IEC 60947-2

[Uimp] rated impulse withstand voltage: 8 kV conforming to IEC 60947-2

[Ics] rated service breaking capacity: 30 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2; 40 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2; 50 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2; 50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2; 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2

[Icw] rated short-time withstand current: 19.2 kA 1 s conforming to IEC 60947-2

mechanical durability: 10000 cycles

electrical durability: 2000 cycles at 690 V In; 4000 cycles at 690 V In/2; 5000 cycles at 440 V In; 6000 cycles at 440 V In/2

power losses: 10 W

mounting support: Backplate

upside connection: Front

downside connection: Front

connection pitch: 70 mm

protection type: L : for overload protection (long time); I : for instantaneous short-circuit protection

trip unit rating: 630 A at 50 °C

long time pick-up adjustment type Ir: Adjustable 9 settings

long time pick-up adjustment range: 0.4...1 x In

long time delay adjustment type: Adjustable 9 settings

[tr] long-time delay adjustment range: 12.5…600 s at 1.5 x Ir; 0.5…24 s at 6 x Ir; 0.7…16.6 s at 7.2 x Ir

thermal memory: 20 mn

instantaneous pick-up adjustment type Ii: Adjustable

instantaneous pick-up adjustment range: 1.5...10 x Ir

earth-leakage protection: Without

neutral protection setting: No protection (3d); 0.5 x Ir (3d + N/2); 1 x Ir (4d)

zone selective interlocking ZSI: Without

auxiliary contact composition: 1 NO/NC

local signalling: 4 LEDs (red) for fault indication; 1 LED (yellow) for overload

display type: LCD display

type of measurement: Energy meter

width: 280 mm

height: 327 mm

depth: 147 mm

net weight: 18 kg

compatibility code: NS630b

Environment

standards: EN/IEC 60947-2

product certifications: ASTA; ASEFA

pollution degree: 3 conforming to IEC 60947

IP degree of protection: IP40 conforming to IEC 60529

IK degree of protection: IK07 conforming to EN 50102

ambient air temperature for operation: -25…70 °C

ambient air temperature for storage: -40…85 °C

relative humidity: 0…95 %

operating altitude: 0...2000 m without derating; 2000 m...5000 m with derating

Offer Sustainability

EU RoHS Directive: Compliant

Mercury free: Yes

RoHS exemption information: Yes

China RoHS Regulation: Product out of China RoHS scope. Substance declaration for your information