Schneider-Electric
33551
Tariff code:
This product is discontinued.
Please contact us for possible replacement product options.
Link to the manufacturers site: 33551 - circuit breaker Compact NS630bL - Micrologic 5.0 - 630 A - 4 poles 4t
Main
range: ComPact
product name: ComPact NS
range of product: ComPact NS630b...1600
device short name: Compact NS630bL
product or component type: Circuit breaker
device application: Distribution
poles description: 4P
protected poles description: 4D
neutral position: Left
[In] rated current: 630 A at 50 °C
[Ue] rated operational voltage: 690 V AC 50/60 Hz
network type: AC
network frequency: 50/60 Hz
suitability for isolation: Yes conforming to EN/IEC 60947-2
utilisation category: Category A
breaking capacity: 130 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2; 150 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2; 150 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2; 100 kA Icu at 500/525 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity code: L 150 kA 415 V AC
trip unit name: Micrologic 5.0
trip unit technology: Electronic
trip unit protection functions: LSI
control type: Toggle; Rotary handle
mounting mode: Fixed
Complementary
[Ui] rated insulation voltage: 800 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand voltage: 8 kV conforming to IEC 60947-2
[Ics] rated service breaking capacity: 100 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2; 130 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2; 150 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2; 150 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
mechanical durability: 10000 cycles
electrical durability: 2000 cycles at 690 V In; 3000 cycles at 690 V In/2; 3000 cycles at 440 V In; 4000 cycles at 440 V In/2
power losses: 15 W
mounting support: Backplate
upside connection: Front
downside connection: Front
connection pitch: 70 mm
protection type: L : for overload protection (long time); S : for short time short-circuit protection; I : for instantaneous short-circuit protection
trip unit rating: 630 A at 50 °C
long time pick-up adjustment type Ir: Adjustable 9 settings
long time pick-up adjustment range: 0.4...1 x In
long time delay adjustment type: Adjustable 9 settings
[tr] long-time delay adjustment range: 12.5…600 s at 1.5 x Ir; 0.5…24 s at 6 x Ir; 0.7…16.6 s at 7.2 x Ir
thermal memory: 20 mn
short-time pick-up adjustment type Isd: Adjustable 9 settings
[Isd] short-time pick-up adjustment range: 1.5...10 x Ir
short-time delay adjustment type: Adjustable
[tsd] short-time delay adjustment range: 0.1…0.4 s I²t=on; 0…0.4 s I²t=off
instantaneous pick-up adjustment type Ii: Adjustable
instantaneous pick-up adjustment range: Off; 2...15 x In
earth-leakage protection: Without
neutral protection setting: No protection (3d); 0.5 x Ir (3d + N/2); 1 x Ir (4d)
zone selective interlocking ZSI: Without
auxiliary contact composition: 1 NO/NC
local signalling: 4 LEDs (red) for fault indication; 1 LED (yellow) for overload
width: 280 mm
height: 327 mm
depth: 147 mm
net weight: 18 kg
compatibility code: NS630b
Environment
standards: EN/IEC 60947-2
product certifications: ASEFA; ASTA
pollution degree: 3 conforming to IEC 60947
IP degree of protection: IP40 conforming to IEC 60529
IK degree of protection: IK07 conforming to EN 50102
ambient air temperature for operation: -25…70 °C
ambient air temperature for storage: -50…85 °C
relative humidity: 0…95 %
operating altitude: 0...2000 m without derating; 2000 m...5000 m with derating
Offer Sustainability
Sustainable offer status: Green Premium product
EU RoHS Directive: Compliant
Mercury free: Yes
RoHS exemption information: Yes
China RoHS Regulation: Product out of China RoHS scope. Substance declaration for your information
Environmental Disclosure: ENVPEP130103EN
© 2018 Alplan Kft.