Schneider-Electric
140DDM69000
Tariff code:
This product is discontinued.
Please contact us for possible replacement product options.
Link to the manufacturers site: 140DDM69000 - discrete I/O module Modicon Quantum - 4 I - 125 V DC - 4 O solid state
Main
range of product: Modicon Quantum automation platform
product or component type: Mixed discrete I/O module
discrete I/O number: 8
Complementary
discrete input number: 4 1 group of 8
discrete input logic: Sink
addressing requirement: 1 input word; 1 output word
network frequency limits: 47…63 Hz
discrete input voltage: 125 V DC
input voltage limits: 156.2 V including ripple
voltage state 0 guaranteed: 0...36 V
voltage state 1 guaranteed: 88...156.2 V
current state 0 guaranteed: <= 1.2 mA
current state 1 guaranteed: >= 2 mA
response time: 0.5 or 1.5 ms depending on the filter at at state 0 to state 1; 0.5 or 1.5 ms depending on the filter at at state 1 to state 0
discrete output number: 4 1 group of 4
discrete output type: Solid state, isolated
discrete output logic: Source or sink
discrete output voltage: 24...125 V
output voltage limits: 19.2...156.2 V DC typical
maximum load current: <= 16 A per module; <= 4 A per point
maximum voltage drop: <0.75 V 4 A
absolute maximum output: 30 A during 500 ms per point
maximum load capacitance: 0.1 µF 150 V DC; 0.6 µF 24 V DC
maximum leakage current: 1.2 mA 150 V DC
protection type: Internal output protection by 5 A fuse per group; On output by transient voltage suppression; On input by resistor limited
associated fuse rating: 5 A
isolation between group of I/O channels: 1780 Vrms for 1 minute
isolation between group and bus: 2500 Vrms for 1 minute
isolation between channels: 1780 Vrms for 1 minute
fault indication: Overcurrent on output
power dissipation: 0.4 W + (1 x input point on) + (0.75 total output load current)
local signalling: 1 LED (green) for bus communication is present (Active); 1 LED (red) for no voltage in output and input (F); 2 LEDs (red) for fault detected on the output point; 4 LEDs (green) for output is turned on; 4 LEDs (red) for fault detected on the input point
marking: CE
bus current requirement: 350 mA
net weight: 0.3 kg
Environment
resistance to electrostatic discharge: 4 kV contact conforming to IEC 801-2; 8 kV on air conforming to IEC 801-2
resistance to electromagnetic fields: 10 V/m 80…1000 MHz conforming to IEC 801-3
ambient air temperature for operation: 0…60 °C
ambient air temperature for storage: -40…85 °C
relative humidity: 95 % without condensation
operating altitude: <= 5000 m
standards: UL 508; CSA C22.2 No 142; FM Class 1 Division 2
product certifications: cUL
Offer Sustainability
Sustainable offer status: Green Premium product
REACh Regulation: Free of Substances of Very High Concern above the threshold
REACh free of SVHC: Yes
EU RoHS Directive: Pro-active compliance (Product out of EU RoHS legal scope)
Mercury free: Yes
RoHS exemption information: Yes
China RoHS Regulation: X
Environmental Disclosure: ENVPEP071201EN
Circularity Profile: ENVEOLI0712001EN
WEEE: The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins