Skip to main content

Schneider-Electric
140ATI03000

analog input module Modicon Quantum - 8 I thermocouple
Barcode: 3595861126602
Tariff code:

This product is discontinued.

Please contact us for possible replacement product options.

Link to the manufacturers site: 140ATI03000 - analog input module Modicon Quantum - 8 I thermocouple

Main

range of product: Modicon Quantum automation platform

product or component type: Analogue input module

type of filter: Notch filter - 3 dB at 50/60 Hz; Single pole low pass - 3 dB at 20 Hz

Complementary

analogue input number: 8

addressing requirement: 10 input words

analogue input type: Thermocouple: - 210...760 °C for thermocouple J; Thermocouple: - 270...1000 °C for thermocouple E; Thermocouple: - 270...1370 °C for thermocouple K; Thermocouple: - 270...400 °C for thermocouple T; Thermocouple: - 50...1665 °C for thermocouple R; Thermocouple: - 50...1665 °C for thermocouple S

analogue input resolution: 16 bits

absolute accuracy error: +/- 2 °C plus + 0.1 % of reading thermocouple E; +/- 2 °C plus + 0.1 % of reading thermocouple J; +/- 2 °C plus + 0.1 % of reading thermocouple K; +/- 2 °C plus + 0.1 % of reading thermocouple T; +/- 4 °C plus + 0.1 % of reading thermocouple R; +/- 4 °C plus + 0.1 % of reading thermocouple S

linearity error: 1 °C, 0.1 °C, 1 F, 0.1 F - 210...760 °C; 1 °C, 0.1 °C, 1 F, 0.1 F - 270...1000 °C; 1 °C, 0.1 °C, 1 F, 0.1 F - 270...1370 °C; 1 °C, 0.1 °C, 1 F, 0.1 F - 270...400 °C; 1 °C, 0.1 °C, 1 F, 0.1 F - 50...1665 °C

accuracy drift according to temperature: 0.15 µV/°C + 0.0015 % of reading/°C max low level voltage

common mode rejection: > - 120 dB 50/60 Hz

isolation between channels and bus: 1780 V AC for 60 s; 2500 V DC for 60 s

isolation between channels: 300 V DC; 220 V AC

update time: 1000 ms

fault type: Broken wire; Overtacking scale

marking: CE

cold junction compensation: Internal 0…60 °C

local signalling: 1 LED (green) for bus communication is present (Active); 1 LED (red) for external fault; 8 LEDs (green) for channel is turned on; 8 LEDs (red) for channel fault

bus current requirement: 280 mA

power dissipation in W: 1.5 W

module format: Standard

net weight: 0.3 kg

Environment

standards: CSA C22.2 No 142; UL 508

product certifications: cUL; FM Class 1 Division 2

resistance to electrostatic discharge: 4 kV contact conforming to IEC 801-2; 8 kV on air conforming to IEC 801-2

resistance to electromagnetic fields: 10 V/m 80…1000 MHz conforming to IEC 801-3

ambient air temperature for operation: 0…60 °C

ambient air temperature for storage: -40…85 °C

relative humidity: 95 % without condensation

operating altitude: <= 5000 m

Offer Sustainability

Sustainable offer status: Green Premium product

REACh Regulation: Free of Substances of Very High Concern above the threshold

REACh free of SVHC: Yes

EU RoHS Directive: Pro-active compliance (Product out of EU RoHS legal scope)

Mercury free: Yes

RoHS exemption information: Yes

China RoHS Regulation: X

Environmental Disclosure: ENVPEP071201EN

Circularity Profile: ENVEOLI0712001EN

WEEE: The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins