Skip to main content

Schneider-Electric
EZC250H2125

circuit breaker Easypact EZC250H - TMD - 125 A - 2 poles 2d
Barcode: 3303431999743
Tariff code:

This product is discontinued.

Please contact us for possible replacement product options.

Link to the manufacturers site: EZC250H2125 - circuit breaker Easypact EZC250H - TMD - 125 A - 2 poles 2d

Main

range: EasyPact

range of product: EasyPact

product name: EasyPact EZC

product or component type: Circuit breaker

device short name: Easypact EZC250H

circuit breaker name: Easypact EZC250H

device application: Distribution

poles description: 2P

protected poles description: 2t

network type: AC; DC

network frequency: 50/60 Hz

[In] rated current: 250 A at 40 °C

[Ui] rated insulation voltage: 690 V AC 50/60 Hz conforming to IEC 60947-2

[Uimp] rated impulse withstand voltage: 6 kV conforming to IEC 60947-2

[Ue] rated operational voltage: 550 V AC 50/60 Hz conforming to IEC 60947-2; 250 V DC conforming to IEC 60947-2

breaking capacity code: H

breaking capacity: 10 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2; 25 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2; 30 kA Icu at 125 V DC 1P conforming to IEC 60947-2; 30 kA Icu at 250 V DC 2P conforming to IEC 60947-2; 36 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2; 36 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2; 85 kA Icu at 110...130 V AC 50/60 Hz conforming to IEC 60947-2; 85 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2

[Ics] rated service breaking capacity: 5 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2; 15 kA at 125 V DC conforming to IEC 60947-2; 15 kA at 250 V DC conforming to IEC 60947-2; 18 kA at 380 V AC 50/60 Hz conforming to IEC 60947-2; 18 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2; 12.5 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2; 42.5 kA at 110/130 V AC 50/60 Hz conforming to IEC 60947-2; 42.5 kA at 220/230/240 V AC 50/60 Hz conforming to IEC 60947-2

suitability for isolation: Yes conforming to IEC 60947-2

utilisation category: Category A

trip unit name: TM-D

trip unit technology: Thermal-magnetic

trip unit rating: 125 A at 50 °C

protection type: Short-circuit protection; Overload protection

pollution degree: 3 conforming to IEC 60664-1; 3 conforming to IEC 947-1

Complementary

control type: Toggle

mounting mode: Fixed

mounting support: Backplate

upside connection: Front

downside connection: Front

mechanical durability: 10000 cycles

electrical durability: Category A: 5000 cycles 415 V AC 50/60 Hz conforming to IEC 60947-2

connection pitch: 35 mm

local signalling: Positive contact indication

neutral protection setting: Without protection

earth-leakage protection: Without

height: 165 mm

width: 105 mm

depth: 60 mm

market segment: Small commercial

compatibility code: EZC250

Environment

standards: EN/IEC 60947-1; EN/IEC 60947-2; GB/T 14048.2; JIS C8201-2-2

IP degree of protection: IP20 conforming to IEC 60529

IK degree of protection: IK07 conforming to IEC 62262

ambient air temperature for operation: -25…70 °C

ambient air temperature for storage: -35…85 °C

Offer Sustainability

Sustainable offer status: Green Premium product

REACh Regulation: Free of Substances of Very High Concern above the threshold

REACh free of SVHC: Yes

EU RoHS Directive: Compliant

Toxic heavy metal free: Yes

Mercury free: Yes

RoHS exemption information: Yes

China RoHS Regulation: X

Environmental Disclosure: ENVPEP1407009EN

WEEE: The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins

© 2018 Alplan Kft.