Schneider-Electric
C40H37E400
Tariff code: 8536209090
Link to the manufacturers site: C40H37E400 - circuit breaker ComPacT NSX400H, 70 kA at 415 VAC, MicroLogic 7.3 E Vigi trip unit 400 A, 3 poles 3d
Main
Range: ComPacT
product name: ComPacT NSX
Range of product: ComPacT NSX400...630
Device short name: NSX400H
Product or component type: Earth leakage circuit breaker
Device application: Distribution
Poles description: 3P
Protected poles description: 3D
[In] rated current: 400 A at 40 °C
[Ue] rated operational voltage: 440 V AC 50/60 Hz
Network type: AC
Network frequency: 50/60 Hz
Suitability for isolation: Yes conforming to EN/IEC 60947-2
Utilisation category: Category A
Breaking capacity: 100 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2; 70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2; 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2; 50 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2; 35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2; 20 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2; 85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1; 65 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1; 20 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1
Breaking capacity code: H 70 kA 415 V AC
Trip unit name: MicroLogic 7.3 E
Trip unit technology: Electronic
Trip unit protection functions: LSIR
Control type: Toggle
Mounting mode: Fixed
Complementary
[Ui] rated insulation voltage: 500 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage: 8 kV
[Ics] rated service breaking capacity: 100 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2; 70 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2; 65 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2; 50 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2; 11 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2; 10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Mechanical durability: 15000 cycles
Electrical durability: 12000 cycles at 440 V In/2; 6000 cycles at 440 V In; 6000 cycles at 690 V In/2; 3000 cycles at 690 V In
Power dissipation per pole: 25.6 W N; 25.6 W L1 and L3; 22.4 W L2
Mounting support: Backplate
Mounting position: Horizontal and vertical; Flat on the back
Upside connection: Front
Downside connection: Front
Connection pitch: 45 mm
Protection type: L : for overload protection (long time); S : for short time short-circuit protection; I : for instantaneous short-circuit protection; R : for earth-leakage protection
Trip unit rating: 400 A at 40 °C
Long time pick-up adjustment type Ir: Adjustable 9 settings
Long time pick-up adjustment range: 160...400 A
Long time delay adjustment type: Adjustable
[tr] long-time delay adjustment range: 15…400 s at 1.5 x Ir; 0.5…16 s at 6 x Ir; 0.35…11 s at 7.2 x Ir
Thermal memory: 20 minutes before and after tripping
Short-time pick-up adjustment type Isd: Adjustable
[Isd] short-time pick-up adjustment range: 1.5...10 x Ir
Short-time delay adjustment type: Adjustable
[tsd] short-time delay adjustment range: 0…0.4 s I²t=off; 0.1…0.4 s I²t=on
Instantaneous pick-up adjustment type Ii: Adjustable
Instantaneous pick-up adjustment range: 1.5...12 x In
Earth-leakage protection: Integrated
Earth-leakage protection class: Class A
Residual earth-leakage sensitity adjustment type: Adjustable
[IΔn] residual earth-leakage sensitive adjustment: 300 mA; 500 mA; 1 A; 3 A; 5 A; 10 A
Operating mode: OFF using the IΔn rotary switch
Residual earth-leakage time delay adjustment type: Adjustable
[Δt] residual earth-leakage time delay adjustment: 0 ms; 60 ms; 150 ms; 500 ms; 1 s
Zone selective interlocking ZSI: Without
Number of slots: 6 slot(s)
Local signalling: Flashing LED (green) for ready to operate; LED 105 % Ir (red) for overload; LED 90 % Ir (orange) for overload
Display type: LCD display
Type of measurement: Energy meter
Communication of data: Time-stamped histories and event tables; Maintenance indicators; Instantaneous and demand values; Maximeters/minimeters; Protection and alarm settings; Power quality; Energy metering; Demand current and power
Width: 140 mm
Height: 255 mm
Depth: 110 mm
Net weight: 6.05 kg
Compatibility code: NSX400
Environment
Standards: EN/IEC 60947-2
Overvoltage category: Class II
Electrical shock protection class: Class II
Pollution degree: 3 conforming to IEC 60664-1
IP degree of protection: IP40 conforming to IEC 60529
IK degree of protection: IK07 conforming to IEC 62262
Ambient air temperature for operation: -25…70 °C
Ambient air temperature for storage: -40…85 °C
Relative humidity: 0…95 %
Operating altitude: 0...2000 m without derating; 2000 m...5000 m with derating
Packing Units
Unit Type of Package 1: PCE
Number of Units in Package 1: 1
Package 1 Height: 16.8 cm
Package 1 Width: 25.5 cm
Package 1 Length: 14.0 cm
Package 1 Weight: 7.5 kg
Offer Sustainability
REACh Regulation: Reference contains Substances of Very High Concern above the threshold
EU RoHS Directive: Compliant with Exemptions
Environmental Disclosure: ENVPEP2309048EN
Circularity Profile: ENVEOLI2309048EN
WEEE: The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
Halogen content performance: Product contains halogen above thresholds
Silicon free: No
Upgradeability: Yes
Take-back: No
Recycled metal content at CR level: 0
Carbon footprint (kg.eq.CO2 per CR, Total Life cycle) : 475
© 2018 Alplan Kft.