Skip to main content

Schneider-Electric
ATV212WU15N4

variable speed drive ATV212 - 1.5kW - 2hp - 480V - 3ph - EMC class C2 - IP55
Net discounted price 777.38 EUR
Available when ordered (delivery time: 47 working day(s))
Barcode: 3606480322662
Tariff code: 8504409590

Link to the manufacturers site: ATV212WU15N4 - variable speed drive ATV212 - 1.5kW - 2hp - 480V - 3ph - EMC class C2 - IP55

Main

Device short name: ATV212

Product destination: Asynchronous motors

Network number of phases: 3 phases

Motor power kW: 1.5 kW

Motor power hp: 2 hp

Supply voltage limits: 323…528 V

Supply frequency: 50...60 Hz - 5...5 %

Line current: 2.5 A at 480 V; 3.2 A at 380 V

Range of product: Altivar 212

Product or component type: Variable speed drive

Product specific application: Pumps and fans in HVAC

communication port protocol: METASYS N2; APOGEE FLN; Modbus; BACnet; LonWorks

[Us] rated supply voltage: 380...480 V - 15...10 %

EMC filter: Class C2 EMC filter integrated

IP degree of protection: IP55

Complementary

Apparent power: 2.8 kVA at 380 V

Continuous output current: 3.7 A at 380 V; 3.7 A at 460 V

Maximum transient current: 4 A for 60 s

Speed drive output frequency: 0.5…200 Hz

Speed range: 1…10

Speed accuracy: +/- 10 % of nominal slip 0.2 Tn to Tn

Local signalling: 1 LED (red) for DC bus energized

Output voltage: <= power supply voltage

Isolation: Electrical between power and control

Type of cable: Without mounting kit: 1 wire(s)IEC cable at 45 °C, copper 90 °C / XLPE/EPR; Without mounting kit: 1 wire(s)IEC cable at 45 °C, copper 70 °C / PVC; With UL Type 1 kit: 3 wire(s)UL 508 cable at 40 °C, copper 75 °C / PVC

Electrical connection: VIA, VIB, FM, FLA, FLB, FLC, RY, RC, F, R, RES: terminal 2.5 mm² / AWG 14; L1/R, L2/S, L3/T: terminal 6 mm² / AWG 10

Tightening torque: 1.3 N.m, 11.5 lb.in (L1/R, L2/S, L3/T); 0.6 N.m (VIA, VIB, FM, FLA, FLB, FLC, RY, RC, F, R, RES)

Supply: Internal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC +/- 5 %, <10 A, protection type: overload and short-circuit protection; Internal supply: 24 V DC (21…27 V), <200 A, protection type: overload and short-circuit protection

Sampling duration: 2 ms +/- 0.5 ms F discrete; 2 ms +/- 0.5 ms R discrete; 2 ms +/- 0.5 ms RES discrete; 3.5 ms +/- 0.5 ms VIA analog; 22 ms +/- 0.5 ms VIB analog

Response time: FM 2 ms, tolerance +/- 0.5 ms for analog output(s); FLA, FLC 7 ms, tolerance +/- 0.5 ms for discrete output(s); FLB, FLC 7 ms, tolerance +/- 0.5 ms for discrete output(s); RY, RC 7 ms, tolerance +/- 0.5 ms for discrete output(s)

Accuracy: +/- 0.6 % (VIA) for a temperature variation 60 °C; +/- 0.6 % (VIB) for a temperature variation 60 °C; +/- 1 % (FM) for a temperature variation 60 °C

Linearity error: VIA: +/- 0.15 % of maximum value for input; VIB: +/- 0.15 % of maximum value for input; FM: +/- 0.2 % for output

Analogue output type: FM switch-configurable voltage 0...10 V DC, impedance: 7620 Ohm, resolution 10 bits; FM switch-configurable current 0...20 mA, impedance: 970 Ohm, resolution 10 bits

Discrete output type: Configurable relay logic: (FLA, FLC) NO - 100000 cycles; Configurable relay logic: (FLB, FLC) NC - 100000 cycles; Configurable relay logic: (RY, RC) NO - 100000 cycles

Minimum switching current: 3 mA at 24 V DC for configurable relay logic

Maximum switching current: 5 A at 250 V AC on resistive load - cos phi = 1 - L/R = 0 ms (FL, R); 5 A at 30 V DC on resistive load - cos phi = 1 - L/R = 0 ms (FL, R); 2 A at 250 V AC on inductive load - cos phi = 0.4 - L/R = 7 ms (FL, R); 2 A at 30 V DC on inductive load - cos phi = 0.4 - L/R = 7 ms (FL, R)

Discrete input type: F programmable 24 V DC, with level 1 PLC, impedance: 4700 Ohm; R programmable 24 V DC, with level 1 PLC, impedance: 4700 Ohm; RES programmable 24 V DC, with level 1 PLC, impedance: 4700 Ohm

Discrete input logic: Positive logic (source) (F, R, RES), <= 5 V (state 0), >= 11 V (state 1); Negative logic (sink) (F, R, RES), >= 16 V (state 0), <= 10 V (state 1)

Dielectric strength: 3535 V DC between earth and power terminals; 5092 V DC between control and power terminals

Insulation resistance: >= 1 mOhm 500 V DC for 1 minute

Frequency resolution: Display unit: 0.1 Hz; Analog input: 0.024/50 Hz

Communication service: Monitoring inhibitable; Read holding registers (03) 2 words maximum; Read device identification (43); Write multiple registers (16) 2 words maximum; Time out setting from 0.1 to 100 s; Write single register (06)

Option card: Communication card for LonWorks

Functionality: Mid

Specific application: HVAC

Discrete output number: 2

Analogue input number: 2

Analogue input type: VIA switch-configurable voltage: 0...10 V DC 24 V max, impedance: 30000 Ohm, resolution 10 bits; VIB configurable voltage: 0...10 V DC 24 V max, impedance: 30000 Ohm, resolution 10 bits; VIB configurable PTC probe: 0...6 probes, impedance: 1500 Ohm; VIA switch-configurable current: 0...20 mA, impedance: 250 Ohm, resolution 10 bits

Analogue output number: 1

Physical interface: 2-wire RS 485

Connector type: 1 open style; 1 RJ45

Transmission rate: 9600 bps or 19200 bps

Transmission frame: RTU

Number of addresses: 1…247

Data format: 8 bits, 1 stop, odd even or no configurable parity

Type of polarization: No impedance

Asynchronous motor control profile: Voltage/frequency ratio, 5 points; Voltage/frequency ratio - Energy Saving, quadratic U/f; Flux vector control without sensor, standard; Voltage/frequency ratio, automatic IR compensation (U/f + automatic Uo); Voltage/frequency ratio, 2 points

Torque accuracy: +/- 15 %

Transient overtorque: 120 % of nominal motor torque +/- 10 % for 60 s

Acceleration and deceleration ramps: Linear adjustable separately from 0.01 to 3200 s; Automatic based on the load

Motor slip compensation: Adjustable; Not available in voltage/frequency ratio motor control; Automatic whatever the load

Switching frequency: 6...16 kHz adjustable; 12...16 kHz with derating factor

Nominal switching frequency: 12 kHz

Braking to standstill: By DC injection

Network frequency: 47.5...63 Hz

Prospective line Isc: 5 kA

Protection type: Overheating protection: drive; Thermal power stage: drive; Short-circuit between motor phases: drive; Input phase breaks: drive; Overcurrent between output phases and earth: drive; Overvoltages on the DC bus: drive; Break on the control circuit: drive; Against exceeding limit speed: drive; Line supply overvoltage and undervoltage: drive; Line supply undervoltage: drive; Against input phase loss: drive; Thermal protection: motor; Motor phase break: motor; With PTC probes: motor

Width: 215 mm

Height: 297 mm

Depth: 192 mm

Net weight: 7 kg

Environment

Pollution degree: 2 conforming to IEC 61800-5-1

IP degree of protection: IP55 conforming to IEC 61800-5-1; IP55 conforming to IEC 60529

Vibration resistance: 1.5 mm (f= 3…13 Hz) conforming to IEC 60068-2-6; 1 gn (f= 13…200 Hz) conforming to EN/IEC 60068-2-8

Shock resistance: 15 gn for 11 ms conforming to IEC 60068-2-27

Environmental characteristic: Classes 3C1 conforming to IEC 60721-3-3; Classes 3S2 conforming to IEC 60721-3-3

Noise level: 48 dB conforming to 86/188/EEC

Operating altitude: 1000...3000 m limited to 2000 m for the Corner Grounded distribution network with current derating 1 % per 100 m; <= 1000 m without derating

Relative humidity: 5…95 % without condensation conforming to IEC 60068-2-3; 5…95 % without dripping water conforming to IEC 60068-2-3

Ambient air temperature for operation: -10…40 °C (without derating); 40…50 °C (with derating factor)

Operating position: Vertical +/- 10 degree

Product certifications: UL; CSA; NOM 117; C-Tick

Marking: CE

Standards: IEC 61800-3 environments 1 category C1; IEC 61800-3 environments 2 category C1; IEC 61800-3 environments 1 category C3; IEC 61800-5-1; IEC 61800-3 environments 2 category C3; IEC 61800-3; IEC 61800-3 category C2; IEC 61800-3 environments 1 category C3; EN 61800-3 category C3; IEC 61800-5-1; IEC 61800-3 category C3; IEC 61800-3 environments 2 category C2; IEC 61800-3 environments 1 category C1; IEC 61800-3 environments 2 category C3; IEC 61800-3 environments 2 category C2; IEC 61800-3 environments 1 category C2; EN 55011 class A group 1; IEC 61800-3 environments 1 category C2; IEC 61800-3 environments 2 category C1; IEC 61800-3; IEC 61800-3 category C2

Assembly style: With heat sink

Electromagnetic compatibility: Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2; Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3; Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4; 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5; Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6; Voltage dips and interruptions immunity test conforming to IEC 61000-4-11

Regulation loop: Adjustable PI regulator

Ambient air temperature for storage: -25…70 °C

Packing Units

Unit Type of Package 1: PCE

Number of Units in Package 1: 1

Package 1 Height: 28.000 cm

Package 1 Width: 25.500 cm

Package 1 Length: 37.000 cm

Package 1 Weight: 6.725 kg

Unit Type of Package 2: P06

Number of Units in Package 2: 5

Package 2 Height: 75.000 cm

Package 2 Width: 60.000 cm

Package 2 Length: 80.000 cm

Package 2 Weight: 46.625 kg

Offer Sustainability

Sustainable offer status: Green Premium product

REACh Regulation: Reference contains Substances of Very High Concern above the threshold

EU RoHS Directive: Pro-active compliance (Product out of EU RoHS legal scope)

Mercury free: Yes

China RoHS Regulation: X

RoHS exemption information: Yes

Environmental Disclosure: ENVPEP111228EN

Circularity Profile: ENVEOLI111234EN

WEEE: The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins

© 2018 Alplan Kft.