Schneider-Electric
XZBWR2STT24
Tariff code: 8517620000
This product is discontinued.
Please contact us for possible replacement product options.
Link to the manufacturers site: XZBWR2STT24 - Vevőegység 2 PNP kimenettel
Main
Product or component type: Programmable receiver
Device application: Interface to PLC
Product compatibility: Radio transmitter XZBWE
Complementary
function of module: Receiver unit for remote sensor
Maximum number of transceivers: ZigBee: <2
Nominal output current: 0.8 A at 24 V DC
Output type: Transistor PNP
Output contacts: 4 PNP
Time delay range: 0.5 s (tolerance: - 15...15 %)
Starting time: <= 400 ms
Maximum switching current: 200 mA DC
Minimum switching current: 10 mA
[Us] rated supply voltage: 24 V DC - 15...20 %
Maximum voltage drop: <2 V (nominal output current: 200 mA)
Communication port protocol: Zigbee green power at 2.4 GHz
Maximum sensing distance: 100 m in free field; 25 m in a metal enclosure
Response time: < 30 ms after sensor change
Number of channels: 2 per receiver
Utilisation category: DC-13 conforming to EN/IEC 60947-5-1
Maximum power consumption in W: 26 W DC
Breaking capacity: 4.8 W (per output)
Short-circuit protection: 1 A fuse type fast blow
Operating position: Any position without derating
Electrical connection: 1 conductor cable 0.14…2.5 mm² AWG 26...AWG 14 solid without cable end conforming to IEC 60947-1; 2 conductors cable 0.14…1.5 mm² AWG 26...AWG 16 solid without cable end conforming to IEC 60947-1; 1 conductor cable 0.14…4 mm² AWG 26...AWG 12 flexible with cable end conforming to IEC 60947-1; 2 conductors cable 0.14…1.5 mm² AWG 26...AWG 16 flexible with cable end conforming to IEC 60947-1
Tightening torque: 0.5…1 N.m conforming to EN/IEC 60947-1
Housing material: Self-extinguishing plastic
Status LED: 1 LED green for power ON; 1 LED green and yellow for reception signal; 4 LEDs green for output active
Mounting support: 35 mm symmetrical DIN rail conforming to EN/IEC 60715; Mounting plate
Rated short-duration power frequency withstand voltage: 1 kV 50 Hz conforming to EN/IEC 60947-5-1
[Uimp] rated impulse withstand voltage: 0.8 kV
Width: 36 mm
height: 108 mm
Depth: 75 mm
Net weight: 0.13 kg
Marking: CE
Environment
Surge withstand: 0.5 kV differential mode conforming to IEC 61000-4-5; 1 kV common mode conforming to IEC 61000-4-5
Standards: EN/IEC 60947-5-1; EN/IEC 60947-1
Ambient air temperature for storage: -40…70 °C
Relative humidity: 90 % at -20…55 °C, without condensation conforming to ETSI EN 300 328
Vibration resistance: +/- 7.5 mm (f= 5…14 Hz) conforming to IEC 60068-2-6; 2 gn (f= 8…150 Hz) conforming to IEC 60068-2-6
Shock resistance: 10 gn (duration = 16 ms) for 6000 shocks conforming to IEC 60068-2-27
IP degree of protection: IP20 (casing) conforming to IEC 60529; IP20 (terminals) conforming to IEC 60529
Pollution degree: 2 conforming to IEC 60664-1
Overvoltage category: III conforming to IEC 60664-1
Insulation resistance: > 500 MOhm at 500 V DC conforming to NF C 20-030
[Ui] rated insulation voltage: 60 V conforming to IEC 60664-1
Electromagnetic compatibility: Immunity for industrial environments conforming to EN/IEC 61000-6-2; Conducted and radiated emissions class B conforming to CISPR 22; Electrostatic discharge immunity test 8 kV in free air (in insulating parts) conforming to IEC 61000-4-2; Electrostatic discharge immunity test 6 kV on contact (on metal parts) conforming to IEC 61000-4-2; Susceptibility to electromagnetic fields 10 V/m, 80 MHz...1 GHz at 3 m conforming to IEC 61000-4-3; Susceptibility to electromagnetic fields 3 V/m, 1.4 MHz…2 GHz at 3 m conforming to IEC 61000-4-3; Electrical fast transient/burst immunity test 2 kV power supply wires conforming to IEC 61000-4-4; Conducted RF disturbances 10 V conforming to IEC 61000-4-6; Radiated emission conforming to ETSI EN 301 489-17; Conducted emission conforming to ETSI EN 301 489-17; Radiated emission conforming to ETSI EN 300 328; Electrical fast transient/burst immunity test 1 kV PNP output wires conforming to IEC 61000-4-4; 1.2/50 µs shock waves immunity test 0.5 kV differential mode conforming to IEC 61000-4-5; 1.2/50 µs shock waves immunity test 1 kV common mode conforming to IEC 61000-4-5; Immunity to microbreaks and voltage drops 7 ms conforming to IEC 61000-4-11
Packing Units
Unit Type of Package 1: PCE
Number of Units in Package 1: 1
Package 1 Height: 13.0 cm
Package 1 Width: 9.8 cm
Package 1 Length: 4.4 cm
Package 1 Weight: 128.0 g
Unit Type of Package 2: S02
Number of Units in Package 2: 22
Package 2 Height: 15.0 cm
Package 2 Width: 30.0 cm
Package 2 Length: 40.0 cm
Package 2 Weight: 3.137 kg
Offer Sustainability
REACh Regulation: Reference contains Substances of Very High Concern above the threshold
EU RoHS Directive: Pro-active compliance (Product out of EU RoHS legal scope)
Mercury free: Yes
RoHS exemption information: Yes
© 2018 Alplan Kft.