XMLR001G1P25
Tariff code: 9032200090
Link to the manufacturers site: XMLR001G1P25 - NYOMÁSKAPCSOLÓ 1 BAR 24VDC 4-20MA 1 PNP
Main
Range of produc: Telemecanique Pressure sensors XM
Product or component type: Electronic pressure sensors
Pressure sensor type: Pressure transmitter
Pressure switch type of operation: Pressure transmitter with 1 switching output
Device short name: XMLR
Pressure rating: 1 bar; 99.97 kPa; 100 kPa
Maximum permissible accidental pressure: 7.5 bar; 750 kPa; 751.53 kPa
Destruction pressure: 751.53 kPa; 7.5 bar; 750 kPa
Controlled fluid: Fresh water (0…80 °C); Air (-20…80 °C); Hydraulic oil (-20…80 °C); Refrigeration fluid (-20…80 °C)
Fluid connection type: G 1/4 (female) conforming to DIN 3852-Y
[Us] rated supply voltage: 24 V DC SELV (voltage limits: 17…33 V)
Complementary
Current consumption: <= 50 mA
Electrical connection: Male connector M12, 4 pins
Analogue output function: 4...20 mA
type of output signal: Analogue + discrete
Analogue output function: 4...20 mA
Discrete output type: Solid state PNP, NO/NC programmable
Maximum switching current: 250 mA
Contacts type and composition: NO/NC programmable
Scale type: Fixed differential
maximum voltage drop: 2 V
Adjustable range of switching point on rising pressure: 0.08…1 bar; 8…100 kPa; 8.00…99.97 kPa
Adjustable range of switching point on falling pressure: 5…97 kPa; 0.05…0.97 bar; 5.03…97.22 kPa
Minimum differential travel: 0.03 bar; 2.96 kPa; 3 kPa
Materials in contact with fluid: 316L stainless steel; Ceramic; Fluorocarbon FKM (Viton)
Front material: Polyester
Housing material: 316L stainless steel; Polyacrylamide
Operating position: Any position, but disposals can falsified the measurement in case of upside down mounting
Protection type: Reverse polarity; Overvoltage protection; Short-circuit protection; Overload protection
Response time on output: <= 10 ms for analog output; <= 5 ms for discrete output
Time delay range: 0...50 s in steps of 1 second
Display type: 4 digits 7 segments
Local signalling: 1 LED (yellow) for light ON when switch is actuated
Display response time type: Fast 50 ms; Normal 200 ms; Slow 600 ms
Maximum delay first up: 300 ms
Accuracy: <= 1 % of the measuring range
linearity error: <= 0.5 % of the measuring range
Hysteresis: <= 0.2 % of the measuring range
Measurement accuracy: <= 0.6 % of the measuring range
Repeat accuracy: <= 0.2 % of the measuring range
drift of the sensitivity: +/- 0.03 % of measuring range/°C
Drift of the zero point: +/- 0.1 % of measuring range/°C
display accuracy: <= 1 % of the measuring range
Mechanical durability: 10000000 cycles
Depth: 42 mm
height: 93 mm
Width: 41 mm
Net weight: 0.19 kg
[Uimp] rated impulse withstand voltage: 0.5 kV DC
Electromagnetic compatibility: Susceptibility to electromagnetic fields: 10 V/m 80...2000 MHz conforming to EN/IEC 61000-4-3; Immunity to conducted RF disturbances: 10 V 0.15...80 MHz conforming to EN/IEC 61000-4-6; Surge immunity test: 1 kV conforming to EN/IEC 61000-4-5; Electrical fast transient/burst immunity test: 2 kV conforming to EN/IEC 61000-4-4; Electrostatic discharge immunity test: 8 kV air, 4 kV contact conforming to EN/IEC 61000-4-2
Controlled fluid: Air,hydraulic oil,fresh water,refrigeration fluid
Temperature of controlled fluid: -20…80 °C
Environment
Marking: CE
product certifications: cULus; EAC
Standards: EN/IEC 61326-2-3; UL 61010-1
ambient air temperature for operation: -20…80 °C
Ambient air temperature for storage: -40…80 °C
IP degree of protection: IP65 conforming to EN/IEC 60529; IP67 conforming to EN/IEC 60529
Vibration resistance: 20 gn (f= 10…2000 Hz) conforming to EN/IEC 60068-2-6
Shock resistance: 50 gn conforming to EN/IEC 60068-2-27
Packing Units
Unit Type of Package 1: PCE
Number of Units in Package 1: 1
Package 1 Height: 6.5 cm
Package 1 Width: 7.5 cm
Package 1 Length: 13.0 cm
Package 1 Weight: 184.0 g
Unit Type of Package 2: S02
Number of Units in Package 2: 20
Package 2 Height: 15.0 cm
Package 2 Width: 30.0 cm
Package 2 Length: 40.0 cm
Package 2 Weight: 4.02 kg
Offer Sustainability
REACh Regulation: Free of Substances of Very High Concern above the threshold
REACh free of SVHC: Yes
EU RoHS Directive: Pro-active compliance (Product out of EU RoHS legal scope)
Mercury free: Yes
RoHS exemption information: Yes