Skip to main content

Schneider-Electric
LC1D32P7TQ

Mágneskapcsoló, 32A, 230VAC, 50/60Hz
Net discounted price 505.34 EUR
Available when ordered (delivery time: 8 working day(s))
Barcode: 3389110351132
Tariff code: 8536490099

Link to the manufacturers site: LC1D32P7TQ - Mágneskapcsoló, 32A, 230VAC, 50/60Hz

Main

Range: TeSys; TeSys Deca

Range of produc: TeSys Deca

Product or component type: Contactor

Device short name: LC1D

contactor application: Resistive load; Motor control

utilisation category: AC-1; AC-3; AC-3e

Poles description: 3P

[Ue] rated operational voltage: Power circuit: <= 690 V AC 25...400 Hz

[Ie] rated operational current: 32 A (at <60 °C) at <= 440 V AC AC-3 for power circuit; 50 A (at <60 °C) at <= 440 V AC AC-1 for power circuit; 32 A (at <60 °C) at <= 440 V AC AC-3e for power circuit

[Uc] control circuit voltage: 230 V AC 50/60 Hz

Complementary

Motor power kW: 15 kW at 380...400 V AC 50/60 Hz (AC-3); 7.5 kW at 220...230 V AC 50/60 Hz (AC-3); 18.5 kW at 500 V AC 50/60 Hz (AC-3); 18.5 kW at 660...690 V AC 50/60 Hz (AC-3); 15 kW at 415...440 V AC 50/60 Hz (AC-3); 7.5 kW at 400 V AC 50/60 Hz (AC-4); 15 kW at 380...400 V AC 50/60 Hz (AC-3e); 7.5 kW at 220...230 V AC 50/60 Hz (AC-3e); 18.5 kW at 500 V AC 50/60 Hz (AC-3e); 18.5 kW at 660...690 V AC 50/60 Hz (AC-3e); 15 kW at 415...440 V AC 50/60 Hz (AC-3e)

Motor power hp: 2 hp at 115 V AC 50/60 Hz for 1 phase motors conforming to CSA; 2 hp at 115 V AC 50/60 Hz for 1 phase motors conforming to UL; 20 hp at 460/480 V AC 50/60 Hz for 3 phases motors conforming to CSA; 20 hp at 460/480 V AC 50/60 Hz for 3 phases motors conforming to UL; 25 hp at 575/600 V AC 50/60 Hz for 3 phases motors conforming to CSA; 25 hp at 575/600 V AC 50/60 Hz for 3 phases motors conforming to UL; 10 hp at 200/208 V AC 50/60 Hz for 3 phases motors conforming to CSA; 10 hp at 200/208 V AC 50/60 Hz for 3 phases motors conforming to UL; 10 hp at 230...240 V AC 50/60 Hz for 3 phases motors conforming to CSA; 10 hp at 230...240 V AC 50/60 Hz for 3 phases motors conforming to UL; 5 hp at 230...240 V AC 50/60 Hz for 1 phase motors conforming to CSA; 5 hp at 230...240 V AC 50/60 Hz for 1 phase motors conforming to UL

Compatibility code: LC1D

Pole contact composition: 3 NO

Protective cover: With

[Ith] conventional free air thermal current: 10 A (at 60 °C) for control circuit; 50 A (at 60 °C) for power circuit

Irms rated making capacity: 140 A AC for control circuit conforming to IEC 60947-5-1; 450 A at 440 V for power circuit conforming to IEC 60947

Rated breaking capacity: 450 kA at 440 V for power circuit conforming to IEC 60947

Associated fuse rating: 10 A gG for control circuit conforming to IEC 60947-5-1; 63 A at <= 690 V coordination type 1 for power circuit; 63 A at <= 690 V coordination type 2 for power circuit

Average impedance: 2 mOhm - Ith 50 A 50 Hz for power circuit

Power dissipation per pole: 2 W AC-3; 5 W AC-1; 2 W AC-3e

[Ui] rated insulation voltage: Control circuit: 600 V CSA certified; Control circuit: 600 V UL certified; Power circuit: 600 V CSA certified; Power circuit: 600 V UL certified; Control circuit: 690 V conforming to IEC 60947-4-1; Power circuit: 690 V conforming to IEC 60947-4-1

Overvoltage category: III

[Uimp] rated impulse withstand voltage: 6 kV conforming to IEC 60947

Safety reliability level: B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1; B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1

Mechanical durability: 15000000 cycles

Control circuit type: AC at 50/60 Hz

Coil technology: Without built-in bidirectional peak limiting diode suppressor

Control circuit voltage limits: 0.3...0.6 Uc (60 °C):drop-out AC 50/60 Hz; 0.8...1.1 Uc (60 °C):operational AC 50 Hz; 0.85...1.1 Uc (60 °C):operational AC 60 Hz

Inrush power in VA: 70 VA cos phi 0.75 (at 20 °C)

Hold-in power consumption in VA: 7 VA 50/60 Hz cos phi 0.3 (at 20 °C)

Heat dissipation: 2…3 W at 50/60 Hz for control circuit

Operating time: 4...19 ms opening; 12...22 ms closing

Maximum operating rate: 3600 cyc/h 60 °C

Connections - terminals: Control circuit: screw clamp terminal 1 1…4 mm² - cable stiffness: solid without cable end; Control circuit: screw clamp terminal 2 1…4 mm² - cable stiffness: solid without cable end; Control circuit: screw clamp terminal 1 1…4 mm² - cable stiffness: flexible without cable end; Control circuit: screw clamp terminal 2 1…4 mm² - cable stiffness: flexible without cable end; Control circuit: screw clamp terminal 1 1…4 mm² - cable stiffness: flexible with cable end; Control circuit: screw clamp terminal 2 1…2.5 mm² - cable stiffness: flexible with cable end; Power circuit: screw clamp terminal 1 1.5…10 mm² - cable stiffness: solid without cable end; Power circuit: screw clamp terminal 2 2.5…10 mm² - cable stiffness: solid without cable end; Power circuit: screw clamp terminal 1 2.5…10 mm² - cable stiffness: flexible without cable end; Power circuit: screw clamp terminal 2 2.5…10 mm² - cable stiffness: flexible without cable end; Power circuit: screw clamp terminal 1 1…10 mm² - cable stiffness: flexible with cable end; Power circuit: screw clamp terminal 2 1.5…6 mm² - cable stiffness: flexible with cable end

Tightening torque: Control circuit: 1.7 N.m - with screwdriver flat Ø 6 mm; Control circuit: 1.7 N.m - with screwdriver Philips No 2; Power circuit: 2.5 N.m - with screwdriver flat Ø 6 mm; Power circuit: 2.5 N.m - with screwdriver Philips No 2; Control circuit: 1.7 N.m - with screwdriver pozidriv No 2; Power circuit: 2.5 N.m - with screwdriver pozidriv No 2

Auxiliary contact composition: 1 NO + 1 NC

Minimum switching voltage: 17 V for control circuit

Minimum switching current: 5 mA for control circuit

Insulation resistance: > 10 MOhm for control circuit

Non-overlap time: 1.5 ms on de-energisation between NC and NO contacts; 1.5 ms on energisation between NC and NO contacts

mounting support: Rail; Plate

Environment

Standards: CSA C22.2 No 14; EN/IEC 60947-5-1; EN/IEC 60947-4-1; UL 508; IEC 60335-1

product certifications: UL; CCC; BV; CSA; GOST; DNV; GL; RINA; LROS (Lloyds register of shipping); UKCA

IP degree of protection: IP2X conforming to IEC 60529; IP2X conforming to VDE 0106

Climatic withstand: conforming to IACS E10 exposure to damp heat; conforming to IEC 60947-1 Annex Q category D exposure to damp heat

Permissible ambient air temperature around the device: -5…60 °C; -40…70 °C at Uc

Operating altitude: 3000 m without derating

Fire resistance: 850 °C conforming to IEC 60695-2-1

Flame retardance: V1 conforming to UL 94

Mechanical robustness: Shocks contactor closed (15 Gn for 11 ms) ; Shocks contactor opened (8 Gn for 11 ms) ; Vibrations contactor opened (2 Gn, 5...300 Hz) ; Vibrations contactor closed (4 Gn, 5...300 Hz)

height: 85 mm

Width: 45 mm

Depth: 92 mm

Net weight: 3.75 kg

Quantity per set: Set of 10

Packing Units

Unit Type of Package 1: PCE

Number of Units in Package 1: 1

Package 1 Height: 4.500 cm

Package 1 Width: 8.500 cm

Package 1 Length: 9.200 cm

Package 1 Weight: 396.000 g

Unit Type of Package 2: S02

Number of Units in Package 2: 24

Package 2 Height: 15.000 cm

Package 2 Width: 30.000 cm

Package 2 Length: 40.000 cm

Package 2 Weight: 10.002 kg

Unit Type of Package 3: P06

Number of Units in Package 3: 384

Package 3 Height: 75.000 cm

Package 3 Width: 60.000 cm

Package 3 Length: 80.000 cm

Package 3 Weight: 166.240 kg

Offer Sustainability

Sustainable offer status: Green Premium product

REACh Regulation: Free of Substances of Very High Concern above the threshold

REACh free of SVHC: Yes

EU RoHS Directive: Compliant

Toxic heavy metal free: Yes

Mercury free: Yes

China RoHS Regulation:  Pro-active China RoHS declaration (out of China RoHS legal scope)

RoHS exemption information: Yes

Environmental Disclosure: ENVPEP110229EN

Circularity Profile: ENVEOLI110229EN

WEEE: The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins

PVC free: Yes

© 2018 Alplan Kft.