Schneider-Electric
140ATI03000
Tariff code:
This product is discontinued.
Please contact us for possible replacement product options.
Link to the manufacturers site: 140ATI03000 - analog input module Modicon Quantum - 8 I thermocouple
Main
range of product: Modicon Quantum automation platform
product or component type: Analogue input module
type of filter: Notch filter - 3 dB at 50/60 Hz; Single pole low pass - 3 dB at 20 Hz
Complementary
analogue input number: 8
addressing requirement: 10 input words
analogue input type: Thermocouple: - 210...760 °C for thermocouple J; Thermocouple: - 270...1000 °C for thermocouple E; Thermocouple: - 270...1370 °C for thermocouple K; Thermocouple: - 270...400 °C for thermocouple T; Thermocouple: - 50...1665 °C for thermocouple R; Thermocouple: - 50...1665 °C for thermocouple S
analogue input resolution: 16 bits
absolute accuracy error: +/- 2 °C plus + 0.1 % of reading thermocouple E; +/- 2 °C plus + 0.1 % of reading thermocouple J; +/- 2 °C plus + 0.1 % of reading thermocouple K; +/- 2 °C plus + 0.1 % of reading thermocouple T; +/- 4 °C plus + 0.1 % of reading thermocouple R; +/- 4 °C plus + 0.1 % of reading thermocouple S
linearity error: 1 °C, 0.1 °C, 1 F, 0.1 F - 210...760 °C; 1 °C, 0.1 °C, 1 F, 0.1 F - 270...1000 °C; 1 °C, 0.1 °C, 1 F, 0.1 F - 270...1370 °C; 1 °C, 0.1 °C, 1 F, 0.1 F - 270...400 °C; 1 °C, 0.1 °C, 1 F, 0.1 F - 50...1665 °C
accuracy drift according to temperature: 0.15 µV/°C + 0.0015 % of reading/°C max low level voltage
common mode rejection: > - 120 dB 50/60 Hz
isolation between channels and bus: 1780 V AC for 60 s; 2500 V DC for 60 s
isolation between channels: 300 V DC; 220 V AC
update time: 1000 ms
fault type: Broken wire; Overtacking scale
marking: CE
cold junction compensation: Internal 0…60 °C
local signalling: 1 LED (green) for bus communication is present (Active); 1 LED (red) for external fault; 8 LEDs (green) for channel is turned on; 8 LEDs (red) for channel fault
bus current requirement: 280 mA
power dissipation in W: 1.5 W
module format: Standard
net weight: 0.3 kg
Environment
standards: CSA C22.2 No 142; UL 508
product certifications: cUL; FM Class 1 Division 2
resistance to electrostatic discharge: 4 kV contact conforming to IEC 801-2; 8 kV on air conforming to IEC 801-2
resistance to electromagnetic fields: 10 V/m 80…1000 MHz conforming to IEC 801-3
ambient air temperature for operation: 0…60 °C
ambient air temperature for storage: -40…85 °C
relative humidity: 95 % without condensation
operating altitude: <= 5000 m
Offer Sustainability
Sustainable offer status: Green Premium product
REACh Regulation: Free of Substances of Very High Concern above the threshold
REACh free of SVHC: Yes
EU RoHS Directive: Pro-active compliance (Product out of EU RoHS legal scope)
Mercury free: Yes
RoHS exemption information: Yes
China RoHS Regulation: X
Environmental Disclosure: ENVPEP071201EN
Circularity Profile: ENVEOLI0712001EN
WEEE: The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins