Schneider-Electric
XENT1192
Tariff code: 8538909999
Link to the manufacturers site: XENT1192 - single isolating block XEN-T - for control circuit
Main
Range of produc: Harmony XAC
Product or component type: Isolating switch
component name: XENT
Electrical circuit type: Control circuit
Contact block application: Emergency stop push-button
Contact block type: Single
Product compatibility: XACA
Contacts type and composition: 3 NC
Mounting of block: Front mounting
contact operation: Slow-break
Complementary
Connections - terminals: Screw clamp terminals, 1 x 0.5...1 x 2.5 mm² without cable end; Screw clamp terminals, 1 x 0.5...2 x 1.5 mm² with cable end
Mechanical durability: 1000000 cycles
Contact code designation: A600 AC-15, Ue = 240 V, Ie = 3 A conforming to IEC 60947-5-1 appendix A; A600 AC-15, Ue = 600 V, Ie = 1.2 A conforming to IEC 60947-5-1 appendix A; Q600 DC-13, Ue = 250 V, Ie = 0.27 A conforming to IEC 60947-5-1 appendix A; Q600 DC-13, Ue = 600 V, Ie = 0.1 A conforming to IEC 60947-5-1 appendix A
[Ithe] conventional enclosed thermal current: 10 A
[Ui] rated insulation voltage: 400 V (pollution degree 3) conforming to IEC 60947-1
[Uimp] rated impulse withstand voltage: 6 kV conforming to IEC 60947-1
Maximum resistance across terminals: 25 MOhm
Operating force: 14 N
Short-circuit protection: 10 A fuse protection by cartridge fuse type gG
Rated operational power in W: 40 W DC-13 for 1000000 cycles, operating rate <60 cyc/mn at 120 V, load factor = 0.5 (inductive load) conforming to IEC 60947-5-1 appendix C; 48 W DC-13 for 1000000 cycles, operating rate <60 cyc/mn at 48 V, load factor = 0.5 (inductive load) conforming to IEC 60947-5-1 appendix C; 65 W DC-13 for 1000000 cycles, operating rate <60 cyc/mn at 24 V, load factor = 0.5 (inductive load) conforming to IEC 60947-5-1 appendix C
Net weight: 0.05 kg
Environment
Standards: CSA C22.2 No 14; UL 508; EN/IEC 60947-5-1; EN/IEC 60204-32
ambient air temperature for operation: -25…70 °C
Ambient air temperature for storage: -40…70 °C
Vibration resistance: 15 gn (f= 10…500 Hz) conforming to IEC 60068-2-6
Shock resistance: 100 gn conforming to IEC 60068-2-27
Electrical shock protection class: Class II conforming to IEC 61140
Packing Units
Unit Type of Package 1: PCE
Number of Units in Package 1: 1
Package 1 Height: 3.6 cm
Package 1 Width: 4.7 cm
Package 1 Length: 10.1 cm
Package 1 Weight: 67.0 g
Unit Type of Package 2: S01
Number of Units in Package 2: 45
Package 2 Height: 15.0 cm
Package 2 Width: 15.0 cm
Package 2 Length: 40.0 cm
Package 2 Weight: 3.189 kg
Offer Sustainability
REACh Regulation: Reference contains Substances of Very High Concern above the threshold
EU RoHS Directive: Pro-active compliance (Product out of EU RoHS legal scope)
Mercury free: Yes
China RoHS Regulation: X
RoHS exemption information: Yes
WEEE: The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
© 2018 Alplan Kft.