Schneider-Electric
VW3A7255
Tariff code: 8504408490
This product is discontinued.
Please contact us for possible replacement product options.
Link to the manufacturers site: VW3A7255 - active infeed converter - 340 kW - 380...480 V
Main
device short name: AIC
network number of phases: 3 phases
[Us] rated supply voltage: 380...480 V +/- 10 %
network frequency: 50/60 Hz
rated power in W: 340 kW
range compatibility: Altivar 71; Altivar 61
product specific application: Component of the Active Front End; Energy regeneration; Low harmonics
product compatibility: ATV61HC31N4D 380...440 V AC with one variable speed drive; ATV71HC25N4D 380...440 V AC with one variable speed drive; ATV61HC31N4D 480 V AC with one variable speed drive; ATV71HC25N4D 480 V AC with one variable speed drive; ATV61H075N4...C63N4D DC with several variable speed drive on a common DC bus; ATV71H075N4...C50N4D DC with several variable speed drive on a common DC bus
assembly style: Built-in unit
type of cooling: Forced convection
Complementary
line current: 495 A at 400 V; 495 A at 480 V
input power: 342 kW at 400 V; 396 kW at 480 V
continuous output current: 517 A at 400 V; 517 A at 480 V
output voltage: 650 V DC - supply: 380...400 V AC; 720 V DC - supply: 440 V AC; 770 V DC - supply: 480 V AC
thermal losses: 5800 W
max current: 1.20 x nominal current (duration = 60 s); 1.35 x nominal current (duration = 2 s)
maximum voltage drop at rated load: <30 % at 380...400 V, <= 60 s; <40 % at 440 V, <= 60 s; <40 % at 480 V, <= 60 s
communication port protocol: Modbus; CANopen
connector type: 1 RJ45 for Modbus; Male SUB-D 9 on RJ45 for CANopen
option card: Communication bridge
operating position: Vertical +/- 10 degree
height: 950 mm
width: 585 mm
depth: 377 mm
net weight: 140 kg
compatibility code: AIC
Environment
environmental characteristic: 3K3 conforming to EN/IEC 60721-3-3; 3C2 conforming to EN 60721-3-3; 3S2 conforming to EN 60721-3-3
relative humidity: 0…95 %
ambient air temperature for operation: 45…60 °C (with current derating of 2 % per °C); -10…45 °C
ambient air temperature for storage: -25…70 °C
operating altitude: <= 1000 m without derating; 1000...3000 m with current derating 1 % per 100 m
pollution degree: 2 conforming to EN 61800-5-1
vibration resistance: 1.5 mm (f= 3…10 Hz) conforming to EN/IEC 60068-2-6; 0.6 gn (f= 10…200 Hz) conforming to EN/IEC 60068-2-6
shock resistance: 4 gn for 11 ms conforming to EN/IEC 60721-3-3
air flow surface: 1000 cm²
volume of cooling air: 1200 m3/h for power circuit; 330 m3/h for control circuit
IP degree of protection: IP00
standards: EN/IEC 61800-5-1
product certifications: UL (pending); CSA (pending); CE
Packing Units
Number of Units in Package 1: 1
Package 1 Height: 53.0 cm
Package 1 Length: 129.0 cm
Package 1 Weight: 160.0 kg
Package 1 Width: 64.0 cm
Unit Type of Package 1: PCE
Offer Sustainability
Sustainable offer status: Green Premium product
REACh Regulation: Reference contains Substances of Very High Concern above the threshold
EU RoHS Directive: Pro-active compliance (Product out of EU RoHS legal scope)
Mercury free: Yes
RoHS exemption information: Yes
China RoHS Regulation: X
Environmental Disclosure: ENVPEP091204EN
WEEE: The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins