Schneider-Electric
56193
Tariff code: 8536490099
Link to the manufacturers site: 56193 - Earth-leakage relay RH99M with automatic reset - 0.03..30 A - 0..4.5 s - 240 V
Main
Range: VigiPacT
Device short name: RH99M
Product or component type: Monitoring relay
Relay application: Monitoring relay
mounting support: DIN rail
Type of setting: Selector
Residual earth-leakage sensitity adjustment type: Adjustable 9 settings
Earth leakage current: 0.03…30 A
Residual earth-leakage time delay adjustment type: Instantaneous for 0.03 A; Adjustable 9 settings 0…4.5 s for 0.03…30 A
Threshold setting: 0.03...30 A alarm
Range compatibility: VigiPacT TOA earth leakage current sensor; VigiPacT A earth leakage current sensor; VigiPacT L earth leakage current sensor
[Ithe] conventional enclosed thermal current: 8 A
Minimum load: 10 mA at 12 V
[Us] rated supply voltage: 220...240 V AC 50/60 Hz 55...110 %
Power consumption in VA: 4 VA
Network rated voltage: 1000 V - AC at 50/60 Hz (maximum) ; 1000 V - AC at 400 Hz (maximum)
Earthing system: TT; TN-S
[Uimp] rated impulse withstand voltage: 8 kV
Complementary
Test function: Local; Remote test
Monitoring: Electronics (continuous) ; Power supply (continuous) ; Relay/sensor link (continuous)
Type of measurement: Earth fault current internal measurement, range: 80...100 %
Tamperproof of settings: Protected by sealable cover
Connections - terminals: Auxiliary power supply: terminal block cable(s) 0.2…2.5 mm² flexible AWG 24...AWG 12; Auxiliary power supply: terminal block cable(s) 0.2…2.5 mm² rigid AWG 24...AWG 12; Auxiliary power supply: terminal block cable(s) 0.25…2.5 mm² flexible with ferrule AWG 24...AWG 12; Fault: screw terminal cable(s) 0.2…2.5 mm² flexible AWG 24...AWG 12; Fault: screw terminal cable(s) 0.2…4 mm² rigid AWG 24...AWG 12; Fault: screw terminal cable(s) 0.25…2.5 mm² flexible with ferrule AWG 24...AWG 12; Relay test and fault reset: screw terminal cable(s) 0.14…1 mm² flexible AWG 26...AWG 16; Relay test and fault reset: screw terminal cable(s) 0.14…1.5 mm² rigid AWG 26...AWG 16; Relay test and fault reset: screw terminal cable(s) 0.25…0.5 mm² flexible with ferrule AWG 26...AWG 16; Sensor: screw terminal cable(s) 0.14…1 mm² flexible AWG 26...AWG 16; Sensor: screw terminal cable(s) 0.14…1.5 mm² rigid AWG 26...AWG 16; Sensor: screw terminal cable(s) 0.25…0.5 mm² flexible with ferrule AWG 26...AWG 16; Voltage presence: screw terminal cable(s) 0.2…2.5 mm² flexible AWG 24...AWG 12; Voltage presence: screw terminal cable(s) 0.2…4 mm² rigid AWG 24...AWG 12; Voltage presence: screw terminal cable(s) 0.25…2.5 mm² flexible with ferrule AWG 24...AWG 12
Wire stripping length: Auxiliary power supply: 7 mm for top connection; Fault: 8 mm for bottom connection; Relay test and fault reset: 5 mm for bottom connection; Sensor: 5 mm for top connection; Voltage presence: 8 mm for bottom connection
Tightening torque: Auxiliary power supply: 0.6 N.m top; Fault: 0.6 N.m bottom; Relay test and fault reset: 0.25 N.m bottom; Sensor: 0.25 N.m top; Voltage presence: 0.6 N.m bottom
9 mm pitches: 6
Standards: EN/IEC 60947-2 Annex M; EN/IEC 60755; UL 1053; CAN/CSA C22.2 No. 144
Width: 54 mm
height: 81 mm
Depth: 74 mm
Net weight: 0.3 kg
IP degree of protection: IP40 on front face: conforming to EN/IEC 60529; IP30 on side parts: conforming to EN/IEC 60529; IP20 on connection terminals: conforming to EN/IEC 60529
IK degree of protection: IK07 conforming to EN 50102
Mechanical robustness: Fire resistance conforming to IEC 60695-2-1; IK protection 2 joules: IK07 conforming to EN 50102; Vibrations 13.2...100 Hz: 0.7 g; Vibrations 2...13.2 Hz: +/- 1 mm
Compatibility code: RH99M
Environment
Overvoltage category: IV
Electrical shock protection class: Class II
Electromagnetic compatibility: Conducted and radiated emissions: , B, conforming to CISPR 11; Conducted radio-frequency immunity test: , 3, conforming to IEC 61000-4-6; Electrostatic discharge immunity test: , 4, conforming to IEC 61000-4-2; High-energy conducted susceptibility: , 4, conforming to IEC 61000-4-5; Low-energy conducted susceptibility: , 4, conforming to IEC 61000-4-4; Radiated susceptibility: , 3, conforming to IEC 61000-4-3
Relative humidity: 95 % at 55 °C
Pollution degree: 3 conforming to IEC 60664-1
ambient air temperature for operation: -35…70 °C
Ambient air temperature for storage: -55…85 °C
Packing Units
Unit Type of Package 1: PCE
Number of Units in Package 1: 1
Package 1 Height: 7.8 cm
Package 1 Width: 8.6 cm
Package 1 Length: 9.2 cm
Package 1 Weight: 276.0 g
Unit Type of Package 2: S03
Number of Units in Package 2: 36
Package 2 Height: 30.0 cm
Package 2 Width: 30.0 cm
Package 2 Length: 40.0 cm
Package 2 Weight: 10.423 kg
Offer Sustainability
Sustainable offer status: Green Premium product
REACh Regulation: Reference contains Substances of Very High Concern above the threshold
EU RoHS Directive: Compliant with Exemptions
Mercury free: Yes
China RoHS Regulation: Product out of China RoHS scope. Substance declaration for your information
RoHS exemption information: Yes
Environmental Disclosure: ENVPEP2310022EN
Circularity Profile: ENVEOLI2310022EN
WEEE: The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
PVC free: Yes
© 2018 Alplan Kft.