Skip to main content

Schneider-Electric
LP1K12105BD

TeSys K contactor - 3P - AC-3 <= 440 V 12 A - 1 NO aux. - 24 V DC coil
Net discounted price 30.15 EUR
Available when ordered (delivery time: 11 working day(s))
Barcode: 3389110790894
Tariff code: 8536419089

Link to the manufacturers site: LP1K12105BD - TeSys K contactor - 3P - AC-3 <= 440 V 12 A - 1 NO aux. - 24 V DC coil

Main

Range of produc: TeSys K

Range: TeSys

Product or component type: Contactor

Device short name: LP1K

contactor application: Resistive load; Motor control

Complementary

utilisation category: AC-3; AC-3e; AC-1; AC-4

Poles description: 3P

Pole contact composition: 3 NO

[Ue] rated operational voltage: Power circuit: <= 690 V AC <= 400 Hz; Signalling circuit: <= 690 V AC <= 400 Hz

[Ie] rated operational current: 12 A (at <60 °C) at <= 440 V AC AC-3 for power circuit; 12 A (at <60 °C) at <= 440 V AC AC-3e for power circuit; 20 A (at <60 °C) at <= 690 V AC AC-1 for power circuit

Control circuit type: DC standard

[Uc] control circuit voltage: 24 V DC

Motor power kW: 3 kW at 220...230 V AC 50/60 Hz AC-3; 5.5 kW at 380...415 V AC 50/60 Hz AC-3; 5.5 kW at 440 V AC 50/60 Hz AC-3; 4 kW at 690 V AC 50/60 Hz AC-3; 3 kW at 220...230 V AC 50/60 Hz AC-3e; 5.5 kW at 380...415 V AC 50/60 Hz AC-3e; 5.5 kW at 440 V AC 50/60 Hz AC-3e; 4 kW at 690 V AC 50/60 Hz AC-3e; 3 kW at 220...230 V AC 50/60 Hz AC-4; 5.5 kW at 380...415 V AC 50/60 Hz AC-4; 5.5 kW at 440 V AC 50/60 Hz AC-4

Auxiliary contact composition: 1 NO

[Uimp] rated impulse withstand voltage: 8 kV

Overvoltage category: III

[Ith] conventional free air thermal current: 20 A (at 60 °C) for power circuit; 10 A (at 50 °C) for signalling circuit

Irms rated making capacity: 144 A AC for power circuit conforming to IEC 60947; 110 A AC for signalling circuit conforming to IEC 60947

Rated breaking capacity: 110 A at 440 V conforming to IEC 60947; 80 A at 500 V conforming to IEC 60947; 70 A at 660...690 V conforming to IEC 60947

[Icw] rated short-time withstand current: 115 A 50 °C - 1 s for power circuit; 105 A 50 °C - 5 s for power circuit; 100 A 50 °C - 10 s for power circuit; 75 A 50 °C - 30 s for power circuit; 55 A 50 °C - 1 min for power circuit; 50 A 50 °C - 3 min for power circuit; 25 A 50 °C - >= 15 min for power circuit; 80 A - 1 s for signalling circuit; 90 A - 500 ms for signalling circuit; 110 A - 100 ms for signalling circuit

Associated fuse rating: 25 A gG at <= 440 V for power circuit; 25 A aM for power circuit; 10 A gG for signalling circuit conforming to IEC 60947; 10 A gG for signalling circuit conforming to VDE 0660

Average impedance: 3 mOhm - Ith 20 A 50 Hz for power circuit

[Ui] rated insulation voltage: Power circuit: 600 V conforming to UL 508; Power circuit: 690 V conforming to IEC 60947-4-1; Signalling circuit: 690 V conforming to IEC 60947-4-1; Signalling circuit: 690 V conforming to IEC 60947-5-1; Signalling circuit: 600 V conforming to UL 508; Power circuit: 600 V conforming to CSA C22.2 No 14; Signalling circuit: 600 V conforming to CSA C22.2 No 14

Insulation resistance: > 10 MOhm for signalling circuit

Inrush power in W: 3 W (at 20 °C)

Hold-in power consumption in W: 3 W at 20 °C

Heat dissipation: 1.3 W

Control circuit voltage limits: Operational: 0.8...1.15 Uc (at <50 °C); Drop-out: >= 0.10 Uc (at <50 °C)

Connections - terminals: Solder pins (external diameter: 0.035 mm)

Maximum operating rate: 3600 cyc/h

Auxiliary contacts type: type instantaneous 1 NO

Minimum switching current: 5 mA for signalling circuit

Minimum switching voltage: 17 V for signalling circuit

mounting support: Printed circuit boards

Operating time: 30...40 ms coil energisation and NO closing; 10 ms coil de-energisation and NO opening

Safety reliability level: B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1; B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1

Mechanical durability: 10 Mcycles

Electrical durability: 1.3 Mcycles 12 A AC-3 at Ue <= 440 V; 1.3 Mcycles 12 A AC-3e at Ue <= 440 V; 0.3 Mcycles 20 A AC-1 at Ue <= 690 V; 0.02 Mcycles 72 A AC-4 at Ue <= 440 V

height: 58 mm

Width: 45 mm

Depth: 57 mm

Net weight: 0.225 kg

Compatibility code: LP1K

Environment

Standards: EN/IEC 60947-4-1; EN/IEC 60947-5-1; UL 60947-4-1; UL 60947-5-1; CSA C22.2 No 60947-4-1; CSA C22.2 No 60947-5-1; GB/T 14048.4

product certifications: CB Scheme; CCC; UL; CSA; EAC; CE; UKCA

IP degree of protection: IP2X

Ambient air temperature for operation: -25…50 °C

Ambient air temperature for storage: -50…80 °C

Operating altitude: 2000 m without derating

Flame retardance: V1 conforming to UL 94; Requirement 2 conforming to NF F 16-101; Requirement 2 conforming to NF F 16-102

Packing Units

Unit Type of Package 1: PCE

Number of Units in Package 1: 1

Package 1 Height: 6.6 cm

Package 1 Width: 6.6 cm

Package 1 Length: 6.6 cm

Package 1 Weight: 255.0 g

Offer Sustainability

Sustainable offer status: Green Premium product

REACh Regulation: Free of Substances of Very High Concern above the threshold

REACh free of SVHC: Yes

EU RoHS Directive: Compliant

Toxic heavy metal free: Yes

Mercury free: Yes

China RoHS Regulation:  Pro-active China RoHS declaration (out of China RoHS legal scope)

RoHS exemption information: Yes

Environmental Disclosure: ENVPEP1503003EN

Circularity Profile: ENVEOLI1503003EN

WEEE: The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins