Skip to main content

Schneider-Electric
LC1E120M5

EasyPact TVS contactor 3P(3 NO) - AC-3 - <= 440 V 120A - 220 V AC coil
Net discounted price 181.73 EUR
Available when ordered (delivery time: 8 working day(s))
Barcode: 3606480323676
Tariff code: 8536490099

Link to the manufacturers site: LC1E120M5 - EasyPact TVS contactor 3P(3 NO) - AC-3 - <= 440 V 120A - 220 V AC coil

Main

Range: Easy TeSys

Range of produc: Easy TeSys Control

Product or component type: Contactor

Device short name: LC1E

contactor application: Motor control; Resistive load

utilisation category: AC-3; AC-1

Poles description: 3P

[Ue] rated operational voltage: Power circuit: <= 690 V AC 50/60 Hz

[Ie] rated operational current: 120 A (at <55 °C) at <= 440 V AC AC-3 for power circuit; 150 A (at <55 °C) at <= 440 V AC AC-1 for power circuit

[Uc] control circuit voltage: 220 V AC 50 Hz

Complementary

Motor power kW: 37 kW at 220...230 V AC 50/60 Hz (AC-3); 55 kW at 380...400 V AC 50/60 Hz (AC-3); 59 kW at 415 V AC 50/60 Hz (AC-3); 59 kW at 440 V AC 50/60 Hz (AC-3); 75 kW at 500 V AC 50/60 Hz (AC-3); 80 kW at 660...690 V AC 50/60 Hz (AC-3)

Pole contact composition: 3 NO

[Ith] conventional free air thermal current: 150 A (at 40 °C)

Irms rated making capacity: 1200 A at 440 V AC for power circuit conforming to IEC 60947-4-1

Rated breaking capacity: 960 A at 440 V for power circuit conforming to IEC 60947

[Icw] rated short-time withstand current: 1100 A 40 °C - 10 s for power circuit

Associated fuse rating: 250 A gG at <= 690 V coordination type 1 for control circuit conforming to IEC 60947-5-1; 10 A gG at <= 690 V coordination type 1 for power circuit

Average impedance: 0.6 mOhm - Ith 150 A 50 Hz for power circuit

Power dissipation per pole: 8.6 W AC-3; 14 W AC-1

[Ui] rated insulation voltage: 690 V conforming to IEC 60947-4-1

Overvoltage category: III

Pollution degree: 3

[Uimp] rated impulse withstand voltage: 8 kV coil not connected to the power circuit conforming to IEC 60947

Mechanical durability: 4000000 cycles

Electrical durability: 800000 cycles AC-3; 250000 cycles AC-1

Control circuit type: AC at 50 Hz

Control circuit voltage limits: 0.85...1.1 Uc (-5…55 °C):operational 50 Hz; 0.35...0.55 Uc (-5…55 °C):drop-out 50 Hz

Inrush power in VA: 300 VA 50 Hz cos phi 0.8 (at 20 °C); 300 VA 60 Hz cos phi 0.8 (at 20 °C)

Hold-in power consumption in VA: 22 VA 50 Hz cos phi 0.3 (at 20 °C); 22 VA 60 Hz cos phi 0.3 (at 20 °C)

Heat dissipation: 3…8 W for control circuit

Operating time: 20...50 ms on closing; 6...20 ms on opening

Maximum operating rate: 1200 cyc/h 55 °C

Connections - terminals: Control circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with cable end; Power circuit: screw clamp terminals 1 10…120 mm² - cable stiffness: flexible with cable end; Power circuit: screw clamp terminals 2 20…170 mm² - cable stiffness: flexible with cable end; Power circuit: screw clamp terminals 1 10…120 mm² - cable stiffness: solid without cable end; Power circuit: screw clamp terminals 2 20…170 mm² - cable stiffness: solid without cable end; Control circuit: screw clamp terminals 1 1…2.5 mm² - cable stiffness: flexible without cable end; Control circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible without cable end; Control circuit: screw clamp terminals 1 1…2.5 mm² - cable stiffness: flexible with cable end; Control circuit: screw clamp terminals 1 1…2.5 mm² - cable stiffness: solid without cable end; Control circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: solid without cable end

Tightening torque: Power circuit: 12 N.m; Control circuit: 1.2 N.m

Auxiliary contact composition: 1 NO + 1 NC

Minimum switching voltage: 17 V for control circuit

Minimum switching current: 5 mA for control circuit

Insulation resistance: > 10 MOhm for control circuit

Non-overlap time: 1.5 ms on energisation guaranteed between NC and NO contact; 1.5 ms on de-energisation guaranteed between NC and NO contact

mounting support: DIN rail; Plate

Environment

Standards: IEC 60947-5-1; IEC 60947-4-1; IEC 60947-1

product certifications: EAC; CE

IP degree of protection: IP2X conforming to IEC 60529

Protective treatment: TH (pollution degree 3) conforming to IEC 60068-2-30 test Db

Permissible ambient air temperature around the device: -20…70 °C at Uc; -60…80 °C storage; -5…55 °C operation

Operating altitude: 3000 m without derating

Fire resistance: 850 °C conforming to IEC 60695-2-1

Mechanical robustness: Vibrations contactor open (1.5 Gn, 5...300 Hz) ; Vibrations contactor closed (3 Gn, 5...300 Hz) ; Shocks contactor open (6 Gn for 11 ms) ; Shocks contactor closed (7 Gn for 11 ms)

height: 158 mm

Width: 120 mm

Depth: 132 mm

Net weight: 2.3 kg

Packing Units

Unit Type of Package 1: PCE

Number of Units in Package 1: 1

Package 1 Height: 19.0 cm

Package 1 Width: 17.0 cm

Package 1 Length: 21.0 cm

Package 1 Weight: 2.41 kg

Unit Type of Package 2: S03

Number of Units in Package 2: 2

Package 2 Height: 30 cm

Package 2 Width: 30 cm

Package 2 Length: 40 cm

Package 2 Weight: 5.24 kg

Unit Type of Package 3: P06

Number of Units in Package 3: 24

Package 3 Height: 80.0 cm

Package 3 Width: 80.0 cm

Package 3 Length: 60.0 cm

Package 3 Weight: 70.84 kg

Offer Sustainability

Sustainable offer status: Green Premium product

REACh Regulation: Free of Substances of Very High Concern above the threshold

REACh free of SVHC: Yes

EU RoHS Directive: Compliant

Toxic heavy metal free: Yes

Mercury free: Yes

China RoHS Regulation: X

RoHS exemption information: Yes

Environmental Disclosure: ENVPEP1405005

Circularity Profile: ENVEOLI1405005

WEEE: The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins

© 2018 Alplan Kft.