Skip to main content

Schneider-Electric
LC1D40AM7

TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 40 A - 220 V AC 50/60 Hz coil
Net discounted price 99.34 EUR
Available when ordered (delivery time: 8 working day(s))
Barcode: 3389119408394
Tariff code: 8536490099

Link to the manufacturers site: LC1D40AM7 - TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 40 A - 220 V AC 50/60 Hz coil

Main

Range: TeSys; TeSys Deca

Range of product: TeSys Deca

Product or component type: Contactor

Device short name: LC1D

Contactor application: Resistive load; Motor control

Utilisation category: AC-4; AC-1; AC-3; AC-3e

Poles description: 3P

[Ue] rated operational voltage: Power circuit: <= 690 V AC 25...400 Hz; Power circuit: <= 300 V DC

[Ie] rated operational current: 60 A (at <60 °C) at <= 440 V AC AC-1 for power circuit; 40 A (at <60 °C) at <= 440 V AC AC-3 for power circuit; 40 A (at <60 °C) at <= 440 V AC AC-3e for power circuit

[Uc] control circuit voltage: 220 V AC 50/60 Hz

Complementary

Motor power kW: 18.5 kW at 380...400 V AC 50/60 Hz (AC-3); 11 kW at 220...230 V AC 50/60 Hz (AC-3); 22 kW at 415...440 V AC 50/60 Hz (AC-3); 22 kW at 500 V AC 50/60 Hz (AC-3); 30 kW at 660...690 V AC 50/60 Hz (AC-3); 9 kW at 400 V AC 50/60 Hz (AC-4); 18.5 kW at 380...400 V AC 50/60 Hz (AC-3e); 11 kW at 220...230 V AC 50/60 Hz (AC-3e); 22 kW at 415...440 V AC 50/60 Hz (AC-3e); 22 kW at 500 V AC 50/60 Hz (AC-3e); 30 kW at 660...690 V AC 50/60 Hz (AC-3e)

Motor power hp: 5 hp at 230/240 V AC 50/60 Hz for 1 phase motors; 10 hp at 230/240 V AC 50/60 Hz for 3 phases motors; 30 hp at 575/600 V AC 50/60 Hz for 3 phases motors; 10 hp at 200/208 V AC 50/60 Hz for 3 phases motors; 3 hp at 115 V AC 50/60 Hz for 1 phase motors; 30 hp at 460/480 V AC 50/60 Hz for 3 phases motors

Compatibility code: LC1D

Pole contact composition: 3 NO

Protective cover: With

[Ith] conventional free air thermal current: 10 A (at 60 °C) for signalling circuit; 60 A (at 60 °C) for power circuit

Irms rated making capacity: 140 A AC for signalling circuit conforming to IEC 60947-5-1; 250 A DC for signalling circuit conforming to IEC 60947-5-1; 800 A at 440 V for power circuit conforming to IEC 60947

Rated breaking capacity: 800 A at 440 V for power circuit conforming to IEC 60947

[Icw] rated short-time withstand current: 320 A 40 °C - 10 s for power circuit; 720 A 40 °C - 1 s for power circuit; 72 A 40 °C - 10 min for power circuit; 165 A 40 °C - 1 min for power circuit; 100 A - 1 s for signalling circuit; 120 A - 500 ms for signalling circuit; 140 A - 100 ms for signalling circuit

Associated fuse rating: 10 A gG for signalling circuit conforming to IEC 60947-5-1; 80 A gG at <= 690 V coordination type 1 for power circuit; 80 A gG at <= 690 V coordination type 2 for power circuit

Average impedance: 1.5 mOhm - Ith 60 A 50 Hz for power circuit

Power dissipation per pole: 2.4 W AC-3; 5.4 W AC-1; 2.4 W AC-3e

[Ui] rated insulation voltage: Power circuit: 600 V CSA certified; Power circuit: 600 V UL certified; Signalling circuit: 690 V conforming to IEC 60947-1; Signalling circuit: 600 V CSA certified; Signalling circuit: 600 V UL certified; Power circuit: 690 V conforming to IEC 60947-4-1

Overvoltage category: III

Pollution degree: 3

[Uimp] rated impulse withstand voltage: 6 kV conforming to IEC 60947

Safety reliability level: B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1; B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1

Mechanical durability: 6 Mcycles

Electrical durability: 1.4 Mcycles 60 A AC-1 at Ue <= 440 V; 1.5 Mcycles 40 A AC-3 at Ue <= 440 V; 1.5 Mcycles 40 A AC-3e at Ue <= 440 V

Control circuit type: AC at 50/60 Hz standard

Coil technology: Without built-in suppressor module

Control circuit voltage limits: 0.3...0.6 Uc (-40…70 °C):drop-out AC 50/60 Hz; 0.8...1.1 Uc (-40…60 °C):operational AC 50 Hz; 0.85...1.1 Uc (-40…60 °C):operational AC 60 Hz; 1...1.1 Uc (60…70 °C):operational AC 50/60 Hz

Inrush power in VA: 140 VA 60 Hz cos phi 0.75 (at 20 °C); 160 VA 50 Hz cos phi 0.75 (at 20 °C)

Hold-in power consumption in VA: 13 VA 60 Hz cos phi 0.3 (at 20 °C); 15 VA 50 Hz cos phi 0.3 (at 20 °C)

Heat dissipation: 4…5 W at 50/60 Hz

Operating time: 4...19 ms opening; 12...26 ms closing

Maximum operating rate: 3600 cyc/h 60 °C

Connections - terminals: Control circuit: screw clamp terminals 2 1…2.5 mm² - cable stiffness: flexible with cable end; Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible without cable end; Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: flexible without cable end; Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: flexible with cable end; Control circuit: screw clamp terminals 1 1…4 mm² - cable stiffness: solid without cable end; Control circuit: screw clamp terminals 2 1…4 mm² - cable stiffness: solid without cable end; Power circuit: EverLink BTR screw connectors 1 1…35 mm² - cable stiffness: flexible without cable end; Power circuit: EverLink BTR screw connectors 2 1…25 mm² - cable stiffness: flexible without cable end; Power circuit: EverLink BTR screw connectors 1 1…35 mm² - cable stiffness: flexible with cable end; Power circuit: EverLink BTR screw connectors 2 1…25 mm² - cable stiffness: flexible with cable end; Power circuit: EverLink BTR screw connectors 1 1…35 mm² - cable stiffness: solid without cable end; Power circuit: EverLink BTR screw connectors 2 1…25 mm² - cable stiffness: solid without cable end

Tightening torque: Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm; Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2; Power circuit: 8 N.m - on EverLink BTR screw connectors - cable 25…35 mm² hexagonal screw head 4 mm; Power circuit: 5 N.m - on EverLink BTR screw connectors - cable 1…25 mm² hexagonal screw head 4 mm; Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver pozidriv No 2; Power circuit: 2.5 N.m - on screw clamp terminals - with screwdriver pozidriv No 2

Auxiliary contact composition: 1 NO + 1 NC

Auxiliary contacts type: type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1; type mirror contact 1 NC conforming to IEC 60947-4-1

Signalling circuit frequency: 25...400 Hz

Minimum switching voltage: 17 V for signalling circuit

Minimum switching current: 5 mA for signalling circuit

Insulation resistance: > 10 MOhm for signalling circuit

Non-overlap time: 1.5 ms on de-energisation between NC and NO contact; 1.5 ms on energisation between NC and NO contact

Mounting support: Plate; Rail

Contact compatibility: M2

Environment

Standards: EN 60947-4-1; EN 60947-5-1; IEC 60947-4-1; IEC 60947-5-1; CSA C22.2 No 14; UL 60947-4-1; IEC 60335-2-40:Annex JJ; UL 60335-2-40:Annex JJ; IEC 60335-1:Clause 30.2

Product certifications: CCC; UL; CB Scheme; CSA; CE; UKCA; Marine; EAC

IP degree of protection: IP20 front face conforming to IEC 60529

Protective treatment: TH conforming to IEC 60068-2-30

Climatic withstand: conforming to IACS E10 exposure to damp heat; conforming to IEC 60947-1 Annex Q category D exposure to damp heat

Permissible ambient air temperature around the device: -40…60 °C; 60…70 °C with derating

Operating altitude: 0...3000 m

Fire resistance: 850 °C conforming to IEC 60695-2-1

Flame retardance: V1 conforming to UL 94

Mechanical robustness: Vibrations contactor open (2 Gn, 5...300 Hz) ; Vibrations contactor closed (4 Gn, 5...300 Hz) ; Shocks contactor closed (15 Gn for 11 ms) ; Shocks contactor open (10 Gn for 11 ms)

Height: 122 mm

Width: 55 mm

Depth: 120 mm

Net weight: 0.85 kg

Packing Units

Unit Type of Package 1: PCE

Number of Units in Package 1: 1

Package 1 Height: 6.2 cm

Package 1 Width: 13.5 cm

Package 1 Length: 15.2 cm

Package 1 Weight: 915.0 g

Unit Type of Package 2: S02

Number of Units in Package 2: 10

Package 2 Height: 15.0 cm

Package 2 Width: 30.0 cm

Package 2 Length: 40.0 cm

Package 2 Weight: 9.776 kg

Unit Type of Package 3: P06

Number of Units in Package 3: 160

Package 3 Height: 77.0 cm

Package 3 Width: 80.0 cm

Package 3 Length: 60.0 cm

Package 3 Weight: 164.9 kg

Offer Sustainability

Sustainable offer status: Green Premium product

REACh Regulation: Free of Substances of Very High Concern above the threshold

REACh free of SVHC: Yes

EU RoHS Directive: Compliant

Toxic heavy metal free: Yes

Mercury free: Yes

China RoHS Regulation:  Pro-active China RoHS declaration (out of China RoHS legal scope)

RoHS exemption information: Yes

Environmental Disclosure: ENVPEP1503009EN

Circularity Profile: ENVEOLI1503009EN

WEEE: The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins

© 2018 Alplan Kft.